Fire Alarm Systems | Fireray3000

Fireray3000

 

www.boschsecurity.com

 

 

 

 

 

 

 

 

 

u

Monitoring range of 5m to 120m (max. 100m
according to DIN VDE 0833-2)

u

Up to 2 detectors per system controller

u

Two pairs of fire and fault relays (one per detector)

u

Transmitter and receiver integrated into a compact
housing

u

Integral LASER alignment

The Fireray3000 is an optical Linear Smoke Detector
for the detection of light and dark smoke across an
area of 5 m to 120 m (max. 100m according to DIN
VDE 0833-2)
Preferred areas of application are very large and high
halls, e. g. airplane hangars, factory buildings and
similar buildings where the use of point detectors are
not possible.

Functions

The transmitter transmits an invisible infrared light
beam bundled through a lens to the receiver.

S

3m

30m

50m

80m

100m

0,9m

1,5m

2,4m

Beam detection
At a maximum distance of 100 m (According to DIN
VDE 0833-2) the core diameter of the light beam is
3 m. The core diameter is the area of the conical IR
beam in which orderly operation of the system is
possible.

If smoke interrupts the beam, the signal in the receiver
is attenuated depending on the thickness of the
smoke. If an attenuation according to the set threshold
lasts longer than 5 s, an alarm is triggered.
The alarm threshold can be set to 25% or 35% or 50%
with the use of prisms.
Slow changes (e. g. contamination of the optical
system) do not cause false alarms; instead, they are
balanced out by an automatic gain control. Here the
current state of the system is compared with a
reference value and adjusted stepwise in case of
deviations greater than 7%. By default, the comparison
is done every 1.5 hours.
With a comp switch, manual or automatic alarm reset
can be selected.

Certifications and approvals

Region

Certification

Germany

VdS

Fireray3000

Europe

CE

Fireray3000

CPD

0786-CPD-21162 Fireray3000

USA

UL

UROX.S3417 Fireray3000

UL

UROXC.S3417 Fireray3000

CSFM

7260-1508:0105 Fireray3000

Summary of Contents for Fireray3000

Page 1: ...rding to DIN VDE 0833 2 the core diameter of the light beam is 3 m The core diameter is the area of the conical IR beam in which orderly operation of the system is possible If smoke interrupts the beam the signal in the receiver is attenuated depending on the thickness of the smoke If an attenuation according to the set threshold lasts longer than 5 s an alarm is triggered The alarm threshold can ...

Page 2: ...moke to the ceiling The detector must therefore be mounted below an expected heat accumulation This can mean that the benchmark values for DL specified in the table must be exceeded 30 60 cm C B A D installation_for_smoke_plume Pos Description A Ceiling B Mushroom cloud C Heat accumulation D IR beam Since the smoke from a fire does not simply rise straight up but rather spreads like a mushroom clo...

Page 3: ... on use and environmental conditions e g quick fire and spread of smoke Depending on the roof construction flat tilted or gable the detectors and receiver must be arranged according to the roof pitch α and the room height RH so that the light beam runs along the roof in a distance DL see table Parts included Qty Components 1 Control Unit Fireray3000 Linear Smoke Detector 1 Infrared transmitter 1 I...

Page 4: ...en The Netherlands Phone 31 40 2577 284 Fax 31 40 2577 330 emea securitysystems bosch com www boschsecurity com Robert Bosch SEA Pte Ltd Security Systems 11 Bishan Street 21 Singapore 573943 Phone 65 6571 2808 Fax 65 6571 2699 apr securitysystems bosch com www boschsecurity asia Bosch Shanghai Security Systems Ltd 201 Building No 333 Fuquan Road North IBP Changning District Shanghai 200335 China P...

Reviews: