12
en
F01U045275 A5 | 2008.03
Bosch Sicherheitssysteme GmbH
Product designation
Manual conventional detector for use in interior areas, surface-mounted,
resettable:
- FMC-300RW-GSRRD manual call point, red /
- FMC-300RW-GSRBU manual call point, blue
- FMC-300RW-GSRYE manual call point, yellow.
Installation
For installation, see Fig. 1- Fig. 8, page 4, 6.
Connection (see Fig. 3, page 4)
Functional test
X
Press the pane in; see Fig. 9.1.
If an alarm is triggered, the LED is illuminated and the color display in
the window changes from white to red.
To reset the manual call point to its starting position:
1.
Unlock the maintenance flap with the test key and pull it forward; see
Fig. 9.2 and 9.3.
2.
Insert the test key into the top opening and push it down; see Fig. 9.4.
The LED goes out and the color display in the window changes from red
to white.
3.
Return the maintenance flap to its starting position.
Technical specifications
Position
Description
Function
1
b1, a1 / b2, a2 Incoming/outgoing
2
E
Shielding
3
-----------------
End of line resistor (EOL)
Operating voltage
20 V DC (8.5 V DC . . 30 V DC)
Current consumption
specified by the respective security system
Alarm resistor
820 Ohm (+/- 10%, 8.5 to 30 VDC)
Permissible operating
temperature
-25 °C . . +70 °C
Protection class as per EN
60529
IP 54
Dimensions
87 x 87 x 56 mm