background image

6

en | Release Notes for Version 2.01

Analog Addressable Fire Panels

F.01U.075.638 | 08 | 2012.08

Release Notes

Bosch Security Systems, Inc.

2

Release Notes for Version 2.01

2.1

New Features in Version 2.01

The following features apply to both the FPA-1000-UL and the FPA-1000-V2:

New devices: 

 Supports the following new Bosch SLC Devices:

FAA-440-B4 Analog Standard Base 4-inch

FAD-440-B4-ISO Analog Isolator Base 4-inch

FAA-440-B6 Analog Standard Base 6-inch

FAA-440-B6-ISO Analog Isolator Base 6-inch

FAH-440 Analog Heat Detector

FAP-440 Analog Photoelectric Detector

FAP-440-D Analog Dual Ray Photoelectric Detector

FAP-440-DT Analog Dual Ray Multisensor Detector Photo/Heat

FAP-440-DTC Analog Dual Ray Multicriteria Detector Photo/Heat/CO

FAP-440-T Analog Multisensor Detector Photo/Heat

FAP-440-TC Analog Multicriteria Detector Photo/Heat/CO

Number of zones: 

On a standalone panel, the number of zones has been increased to 

225.

Number of floors: 

The number of floors per system has been increased to 64.

Trouble LED during panel initialization: 

During initialization, the panel activates the 

global trouble zone, so outputs assigned to that zone follow the Trouble LED.

New global zone: 

Added global zone for Waterflow.

Increased history event records: 

The maximum number of history event records has 

been increased to 2999.

Walk test timer reset: 

In walk test mode, every activation from an input point restarts 

the 25-minute walk test timer.

Silence at reset: 

 At the beginning of system reset, the panel silences every silenceable 

output according to the silence mode (audible only or audible/visible) programmed for 
the system.

Sandwich Alarm silence/unsilence: 

For sandwich alarms, at each transition the panel 

unsilences if it was silenced during the previous phase.

The following features apply only to the FPA-1000-V2:

Peer-to-peer networking: 

Supports peer-to-peer networking of up to eight FPA-1000-V2 

control panels in a single group using FPE-1000-NE Networking Card 3-Ethermet, FPE-
1000-NF Networking Card 1-Ethernet 2-Fiber Optic, or FPE-1000-NW Networking Card 1-
Ethernet 2-Wired

Number of zones: 

In a networked system, each panel has 128 local zones plus 97 group 

zones and 18 global zones. 

Auto crossover detection: 

Ethernet port on FPA-1000-V2 Mainboard supports automatic 

crossover detection, so connection can be made with either a cross-over cable or a 
straight CAT 5 cable.

IP address and ID display:

 During Lamp Test, holding the ACK button in for more than 3 

seconds displays the panel IP address and ID number on the keypad.

2.2

Issues Fixed in Version 2.01

NAC pattern selection: 

The ability to choose a NAC pattern for the following global zones 

(Alarm Verification, Pre-signal, PAS, and Reset) has ben removed.

Summary of Contents for FPA-1000 Series

Page 1: ...Analog Addressable Fire Panels FPA 1000 en Release Notes ...

Page 2: ......

Page 3: ...ues Fixed in Version 1 13 10 4 3 Known Issues in Version 1 13 10 5 Release Notes for Version 1 12 10 5 1 New Features in Version 1 12 10 5 2 Issues Fixed in Version 1 12 10 5 3 Known Issues in Version 1 12 11 6 Release Notes for Version 1 11 11 6 1 New Features in Version 1 11 11 6 2 Issues Fixed in Version 1 11 11 6 3 Known Issues in Version 1 11 11 7 Release Notes for Version 1 10 11 7 1 New Fea...

Page 4: ...Systems Inc 10 Release Notes for Version 1 01 15 10 1 New Features in Version 1 01 15 10 2 Issues Fixed in Version 1 01 15 10 3 Known Issues in Version 1 01 15 11 Release Notes for Version 1 00 16 11 1 New Features in Version 1 00 16 11 2 Issues Fixed in Version 1 00 16 11 3 Known Issues with Version 1 00 16 ...

Page 5: ... act as one panel The standard control panel supports one Signaling Line Circuit SLC for up to 254 detectors and modules or up to 127 analog sounder bases in combination with a suitable detector for a total of 254 addressable device capacity per SLC The control panel is easily expandable with the FPE 1000 SLC Signaling Line Circuit Plug in Module doubling the address points On the front of the pan...

Page 6: ...imum number of history event records has been increased to 2999 Walk test timer reset In walk test mode every activation from an input point restarts the 25 minute walk test timer Silence at reset At the beginning of system reset the panel silences every silenceable output according to the silence mode audible only or audible visible programmed for the system Sandwich Alarm silence unsilence For s...

Page 7: ...alls non modem result in a trouble message Currently a work around is to disable remote access Only one group allowed Currently although up to eight panels can be networked they must all be in the same group Panels will be assignable to different groups in the next release but in the meantime prevent access to functions silence reset etc by untrained unauthorized personnel Multi building interconn...

Page 8: ...g Addressable Fire Panels F 01U 075 638 08 2012 08 Release Notes Bosch Security Systems Inc Shorted Option Bus Terminals issue If option bus ternimal B gnd and terminal G tx are shorted a transistor may break requiring replacement of the panel ...

Page 9: ...n corrected SLC intermittent open issue If the SLC loop is intermittently open and closed troubles will be reported for the wrong devices 3 3 Known Issues in Version 1 14 incorrect temporal pattern FAA 325 B6S may produce an incorrect temporal pattern for the first cycle Reduced system initialization speed On large systems with many FMR 1000 annunciators tupdating annunciator status and initializi...

Page 10: ...pairs Set the maximum co dependent zones of one zone to four different zones Hexadecimal reporting account number Regardless of which reporting format menu web browser is used the panel can be programmed with hexadecimal reporting account numbers Point restoral upon reset Upon panel reset the panel restores all existing alarms including fire waterflow alarms gas alarms and supervisory alarms This ...

Page 11: ...isable remote access New SLC devices The FAP 325 T Analog Multisensor Detector is in the literature as SLC device but is not available yet 6 Release Notes for Version 1 11 6 1 New Features in Version 1 11 No new features introduced in this version 6 2 Issues Fixed in Version 1 11 Phone line 1 troubles In out calls on phone line 1 no longer initiate line disconnect or dialer answering trouble signa...

Page 12: ...panel MMI and Web pages into the languages Portuguese and Spanish New features on the Web pages Off line configuration tool Online help Allows for comparing and printing the programmed configuration Allows timezone offset for time synchronization with PC 7 2 Issues Fixed in Version 1 10 Gas alarm Gas alarms are reported to the central station receiver as event type Fire Supervisory if Modem IIIa2 ...

Page 13: ...he product MMI but replaced by EXT SIGNALING Page 133 The Web login screenshot on the page below shows a RESET button Such button is not available on the product Web page Page 136 The description about the item Compare Configuration does not exactly match the software functionality In fact it should say You can compare either two different FPA 1000 UL configuration files or preview saved unimpleme...

Page 14: ...ass A loop and pressing reset 28 day Auto Test Interval This fixes an issue where the next auto test report is sent approximately 1 hour later than expected when setting the auto test interval to 28 days FAA 325 B6S menu for the detector The menu item Edit Sounder Base for detectors is removed The menu was intended as a shortcut from Add A Device or Edit A Device to Edit Sounder Base when programm...

Page 15: ...mming is disabled 25 minutes later FAA 325 B6S menu for the detector The menu Edit Sounder Base for detectors is not working The menu was intended as a shortcut from Add A Device or Edit A Device to Edit Sounder Base when programming SLC devices 10 Release Notes for Version 1 01 10 1 New Features in Version 1 01 With Version 1 01 the panel s display supports Spanish and Portuguese 10 2 Issues Fixe...

Page 16: ...ctor The menu Edit Sounder Base for detectors is not working The menu was intended as a shortcut from Add A Device or Edit A Device to Edit Sounder Base when programming SLC devices 11 Release Notes for Version 1 00 11 1 New Features in Version 1 00 New product release 11 2 Issues Fixed in Version 1 00 New product release 11 3 Known Issues with Version 1 00 None ...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 USA www boschsecurity us Bosch Security Systems Inc 2012 ...

Reviews: