Bosch Security Systems, Inc.
2
Release Notes for Version 2.01
2.1
New Features in Version 2.01
The following features apply to both the FPA-1000-UL and the FPA-1000-V2:
–
New devices:
Supports the following new Bosch SLC Devices:
–
FAA-440-B4 Analog Standard Base 4-inch
–
FAD-440-B4-ISO Analog Isolator Base 4-inch
–
FAA-440-B6 Analog Standard Base 6-inch
–
FAA-440-B6-ISO Analog Isolator Base 6-inch
–
FAH-440 Analog Heat Detector
–
FAP-440 Analog Photoelectric Detector
–
FAP-440-D Analog Dual Ray Photoelectric Detector
–
FAP-440-DT Analog Dual Ray Multisensor Detector Photo/Heat
–
FAP-440-DTC Analog Dual Ray Multicriteria Detector Photo/Heat/CO
–
FAP-440-T Analog Multisensor Detector Photo/Heat
–
FAP-440-TC Analog Multicriteria Detector Photo/Heat/CO
–
Number of zones:
On a standalone panel, the number of zones has been increased to
225.
–
Number of floors:
The number of floors per system has been increased to 64.
–
Trouble LED during panel initialization:
During initialization, the panel activates the
global trouble zone, so outputs assigned to that zone follow the Trouble LED.
–
New global zone:
Added global zone for Waterflow.
–
Increased history event records:
The maximum number of history event records has
been increased to 2999.
–
Walk test timer reset:
In walk test mode, every activation from an input point restarts
the 25-minute walk test timer.
–
Silence at reset:
At the beginning of system reset, the panel silences every silenceable
output according to the silence mode (audible only or audible/visible) programmed for
the system.
–
Sandwich Alarm silence/unsilence:
For sandwich alarms, at each transition the panel
unsilences if it was silenced during the previous phase.
The following features apply only to the FPA-1000-V2:
–
Peer-to-peer networking:
Supports peer-to-peer networking of up to eight FPA-1000-V2
control panels in a single group using FPE-1000-NE Networking Card 3-Ethermet, FPE-
1000-NF Networking Card 1-Ethernet 2-Fiber Optic, or FPE-1000-NW Networking Card 1-
Ethernet 2-Wired
–
Number of zones:
In a networked system, each panel has 128 local zones plus 97 group
zones and 18 global zones.
–
Auto crossover detection:
Ethernet port on FPA-1000-V2 Mainboard supports automatic
crossover detection, so connection can be made with either a cross-over cable or a
straight CAT 5 cable.
–
IP address and ID display:
During Lamp Test, holding the ACK button in for more than 3
seconds displays the panel IP address and ID number on the keypad.
2.2
Issues Fixed in Version 2.01
–
NAC pattern selection:
The ability to choose a NAC pattern for the following global zones
(Alarm Verification, Pre-signal, PAS, and Reset) has ben removed.