28
en | Maintenance
Conventional Fire Panel
F.01U.172.982 | 5.0 | 2012.04
Operation Guide
Bosch Sicherheitssysteme GmbH
6
Maintenance
Keep a log book that includes the following data as a minimum:
–
Information on the monitored object
–
Contact details of the maintenance company
–
Events
Record all events, such as alarms, faults and services, in this log
book.
Ensure that an inspection is carried out on your fire detection
system four times a year at roughly regular intervals.
Ensure that the following function checks are carried out during
the inspection:
–
Trigger an automatic detector for each zone to check the
transmission lines and notification appliances
–
Test the condition of the batteries and the function of the
power supply unit
–
Check the log book
Record the inspection and the results in the log book.
Carry out the following additional checks at least once a year:
–
Check all elements of the fire panel
–
Trigger all detectors that can be tested without being
damaged
–
Visually check all cabling and elements
NOTICE!
–
Have maintenance and inspection work carried out
regularly by trained, qualified personnel
–
Please observe the appropriate requirements stipulated by
the local authorities (e.g. fire service)
NOTICE!
Replace the batteries regularly. Please observe the appropriate
requirements stipulated by the local authorities etc.