background image

 

 

 

 

 

Conventional Fire Panel

FPC-500-2 / FPC-500-4 / FPC-500-8

 
 

en

Installation Guide

 

Summary of Contents for FPC-500-2

Page 1: ...Conventional Fire Panel FPC 500 2 FPC 500 4 FPC 500 8 en Installation Guide ...

Page 2: ......

Page 3: ... 3 3 2 Zones 21 3 3 3 Aux power 23 3 3 4 Notification Appliances 24 3 3 5 Relay Outputs 25 3 3 6 Extensions 26 3 3 7 External power supply 26 3 4 Initial Start Up 29 3 4 1 Setting the Language 29 3 4 2 Setting the Time and Date 29 4 System Configuration 31 4 1 System Configuration 34 4 1 1 Setting the Date Time 34 4 1 2 Buzzer Beep 34 4 1 3 EOL Elements 35 4 1 4 Resetting Zones 35 4 1 5 Aux Power ...

Page 4: ...7 2 Notification appliance 2 54 4 7 3 Alarm Relay 55 4 7 4 Fault Relay 55 4 7 5 OC Relay Extension 55 4 7 6 Control all outputs 56 4 8 Resetting To Delivery State 56 5 Fault Diagnosis 58 6 Technical Data 59 6 1 Electrical Data 59 6 1 1 Communication parameters 61 6 2 Mechanical 62 6 3 Environmental Conditions 62 6 4 Information as per EN 54 4 chapter 7 1 63 6 5 Options with requirements as per EN ...

Page 5: ...7 5 Event Memory 76 7 6 Test Memory Messages 78 Index 79 Conventional Fire Panel Table of Contents en 5 Bosch Sicherheitssysteme GmbH 2014 06 7 0 F 01U 172 980 ...

Page 6: ...tes properly Notice Note local regulations when connecting to 230 V power supplies Notice Please observe the country specific regulations and guidelines during planning installation and programming of the fire panel Notice In line with EN 54 13 BOSEC certificate TCC 2 977 each conventional line must be terminated with EOL modules for the operation of fire detection systems The AUX power supply mus...

Page 7: ...n designed for operation in closed rooms Please note the permissible environmental conditions in the technical specifications Conventional Fire Panel Safety Instructions en 7 Bosch Sicherheitssysteme GmbH 2014 06 7 0 F 01U 172 980 ...

Page 8: ...ault Power Fault NAC Fault Disabled Notification Appliance Silent Day Mode Test Disable Power ALARM 4 3 1 2 1 LED display 2 LCD display with zone numbers 3 Zone keys and zone status LEDs 4 Operating panel 2 8 en System Overview Conventional Fire Panel 2014 06 7 0 F 01U 172 980 Bosch Sicherheitssysteme GmbH ...

Page 9: ...mA Alarm device 500 mA each Relay 1 2 2 Extensions Open collector 20 mA Relay via OC no 1 x 4 2 x 4 LCD 2 x 16 characters Yes 230 VAC AUX 24 V DC OC 0 4 8 Z1 Z8 ALARM RLY FAULT RLY IN1 IN2 Conventional Fire Panel System Overview en 9 Bosch Sicherheitssysteme GmbH 2014 06 7 0 F 01U 172 980 ...

Page 10: ...4 8 on FPC 500 8 AUX 24 VDC AUX power supply Features Alarm verification The user is prompted to verify the alarm Intermediate alarm storage an alarm triggered by an automatic detector is reset automatically after 20 seconds adjustable by the panel If there is an additional alarm within 10 minutes in this zone the notification appliances are enabled Otherwise the pre alarm is reset automatically D...

Page 11: ...or or relay outputs freely programmable depending on panel version Quick and easy programming using the keypad and LCD display Easy operation for the end user Two monitored notification appliance outputs EN 54 13 BOSEC certificate TCC 2 977 compliant system by using EOL modules Power supply via power supply unit with thermal fuse Emergency power supply using batteries up to 7 2 Ah reverse polarity...

Page 12: ...date Switch key tones on off Put zones in test mode and take zones out of test mode Switch off on zones notification appliances relay and transistor outputs Trigger evacuations Reset panel Switch between day night mode All actions of level 1 Level 3 All settings for installing and programming the system Code inputs are necessary for accessing level 2 and 3 2 1 12 en System Overview Conventional Fi...

Page 13: ... emergency response teams e g fire department Note permissible environmental conditions Install the fire panel at a height above the ground that permits convenient operation by the user and easy reading of the LCD display Inserting the Cable Route the necessary cables for zones inputs and outputs as well as the power supply etc and carefully punch out the cable entries needed for this Warning Elec...

Page 14: ...ble insertion M 20 x 1 5 screw joints PG13 5 can be used The cable entries on the rear are intended for direct cable entry of flush mounted cables Opening the Housing Remove the cover of the fire panel Loosen both screws on the underside of the housing lift up the cover approx 20 and remove it 3 2 2 14 en Installation Conventional Fire Panel 2014 06 7 0 F 01U 172 980 Bosch Sicherheitssysteme GmbH ...

Page 15: ... drilling jib on the rear of the housing Drill the holes Guide the cables routed under plaster through the punched out cable ducts on the rear of the housing into the housing Mount the housing to the wall using screws Make sure that cables are not pinched Then guide the cables routed on plaster through the cable entries to the upper side of the housing 3x 8 x 40 mm 3x 6 x 50 mm PZ3 S8 3x 6 x 50 mm...

Page 16: ...gulations when connecting to 230 V power supplies Wire up the 230 V power supply to the screw clamp provided on the power supply unit board Use a cable tie to ensure strain relief of the power supply feeder in the housing above the power supply unit Danger Only perform installation work when the panel has no voltage There is a danger of an electric shock N L 230 VAC 50 60 Hz 3 2 4 16 en Installati...

Page 17: ...etween the top of the batteries and the housing There are different emergency current back up times depending on the battery capacity used and the current consumption of the components connected to the panel You can calculate this using the battery calculator included on the CD After troubleshooting a mains fault and operating the fire panel via emergency current the power supply unit switches bac...

Page 18: ...at the maximum line resistance for transistor outputs is 22 5 Ohm The extensions are connected to the left side of the main board Simply connect the board to the plugs Make sure that the plug engages correctly 3 2 6 18 en Installation Conventional Fire Panel 2014 06 7 0 F 01U 172 980 Bosch Sicherheitssysteme GmbH ...

Page 19: ...00 8 Two extensions can be connected Wiring External components such as zones notification appliances inputs etc are wired to screw terminals attached to the upper side of the board 1 2 3 4 5 No Meaning FPC 500 2 FPC 500 4 FPC 500 8 1 Inputs 1 1 2 2 Zones 2 4 8 3 Aux power supply 1 4 Notification appliance 2 5 Alarm and fault relay 1 1 3 3 Conventional Fire Panel Installation en 19 Bosch Sicherhei...

Page 20: ...EC certificate TCC 2 977 the EOL modules Notice Only use resistors with a maximum 1 tolerance The 3 9 kOhm resistors are supplied Inputs IN1 820Ω 5 3 9kΩ The fire panel offers two control inputs You can assign different functions to these depending on programming see Configuring Inputs page 47 The connection terminals IN1 and IN2 are available Notice Note that the maximum line resistance for input...

Page 21: ... supply b a b a 1 ZONE 2 3 9kΩ a b 3 9kΩ b a b a 1 ZONE 2 EOL EOL a b EN 54 13 BOSEC certificate TCC 2 977 Each zone must be completed with a terminal element You can either use a 3 9 kΩ 1 resistor or EOL modules for an EN 54 13 BOSEC certificate TCC 2 977 compliant termination Unused zones must also be terminated with a terminal element Mixing different terminal elements is not allowed 3 3 2 Conv...

Page 22: ...n the CD Notice The last zone of the fire panel supports the use of 4 wire detectors The fire panel does not support dual detector dependency with 4 wire detectors Please use permissible external power supply units depending on power consumption Notice Activating a manual call point in a zone programmed as No Delay triggers an immediate alarm Notice Only use manual call points in zones which are p...

Page 23: ...power must be terminated by a terminal element For EN 54 13 BOSEC certificate TCC 2 977 compliant connection of 4 wire elements the AUX and zone lines must be routed in separate cables You can either use a 3 9 kΩ 1 resistor or EOL modules for EN 54 13 BOSEC certificate TCC 2 977 compliant termination Program the reset behavior of the auxiliary power as described in Aux Power page 37 Notice Note th...

Page 24: ... Note that the maximum line resistance for notification appliances is 22 5 Ohm The fire panel offers you two notification appliance circuit lines that can be used to activate the audible notification appliances and visual notification appliances When there is a fire alarm the notification appliance circuit lines are activated depending on programming 3 3 4 24 en Installation Conventional Fire Pane...

Page 25: ...s The relays work as potential free change over contacts The alarm relay is activated by every fire alarm Notice A transmission device must be installed in the immediate vicinity without a space of the FPC 500 x The connecting line between the fire panel and the transmission device must not be exposed as it is not monitored Notice Both relay outputs ALARM and FAULT can switch a maximum of 1 A 30 V...

Page 26: ...as an external power source for the FPC 500 Fire Panel Notice Note that the FPP 5000 housing must be installed in the direct vicinity without a space of the FPC 500 x The connecting line between the FPP 5000 and the transmission device must not be exposed as it is not monitored FPC 500 2 and FPC 500 4 Wire the FPP 5000 as shown in FPC 500 2 and FPC 500 4 page 26 Program input 1 to Ext PS Fault see...

Page 27: ...BAT1 BAT2 FAULT FAULT AC BAT MAIN POWER MAIN POWER TROUBLE TROUBLE TROUBLE BATTERY 1 BATTERY 2 Σ 1 2 24V 3k9 820 FPC 500 8 Wire the FPP 5000 as shown in FPC 500 8 page 27 Conventional Fire Panel Installation en 27 Bosch Sicherheitssysteme GmbH 2014 06 7 0 F 01U 172 980 ...

Page 28: ... of delivery FPP 5000 12 V 12 V BCM 0000 B 24V 24V MAIN BAT1 BAT2 FAULT FAULT AC BAT MAIN POWER MAIN POWER TROUBLE TROUBLE TROUBLE BATTERY 1 BATTERY 2 Σ 1 2 24V NO Relais 24VDC 1A NC C NO Relais 24VDC 1A NC C 3k9 820 3k9 820 28 en Installation Conventional Fire Panel 2014 06 7 0 F 01U 172 980 Bosch Sicherheitssysteme GmbH ...

Page 29: ...w keys to set the desired language ACK Confirm your selection in the menu with the ACK key Setting the Time and Date Set the current time and date The current time and date are important for functions such as Event memory and Automatic switching to night mode i Use the arrow keys to set the current day ACK Confirm your selection in the menu with the ACK key Repeat this procedure to set the correct...

Page 30: ...re not made automatically Make these settings manually If there is a total power failure you must make the settings for the date and time again 30 en Installation Conventional Fire Panel 2014 06 7 0 F 01U 172 980 Bosch Sicherheitssysteme GmbH ...

Page 31: ...nter the code with zone keys 1 to 8 You are in the programming menu of the system Caution In operating level 3 the fire panel is not operational None of the inputs and outputs are monitored Automatic exit of level 3 If you are in level 3 and no key has been pressed for 10 minutes the system will exit level 3 automatically One minute before exiting level 3 a pulse tone of the internal buzzer indica...

Page 32: ...SET Press the ACK key to exit operating level 3 If you do not want to exit operating level 3 press the RESET key Menu Operating level 3 of the fire panel offers you the following setting options 1 System Config 2 Delay Config 3 Zone Config 4 Input Config 5 Output Config 6 View Config 7 Output Control 8 Config Reset Notice The structure and description of menus of operating levels 1 and 2 can be fo...

Page 33: ...e menus scroll automatically every 2 5 seconds to the next menu item If you would like to select the menu item currently shown simply confirm with the ACK key Navigating with the zone keys 8 1 In the menu each menu item has a number from 1 to 8 preceding it Use the zone keys to select the desired menu item in the menu The desired menu item does not have to be shown in the display Navigating with t...

Page 34: ...ress zone key 1 This takes you to the System Config menu 1 Press zone key 1 You can now set the date and time ACK To save the currently displayed value press the ACK key Repeat the steps to set the month year hour and minute Buzzer Beep 1 Press zone key 1 This takes you to the System Config menu 2 Press zone key 2 This takes you to the Keypad Tone submenu 2 1 Press zone keys 1 or 2 1 On default se...

Page 35: ...select With 4W Module you must specify the threshold for the creeping short circuit You can calculate this using the battery calculator included on the CD Resetting Zones In this menu you can specify the delay times for resetting zones You can specify how long the zones can be disconnected from the power and how long the stabilization time of the detector should last This setting is used for the z...

Page 36: ...1s 2 5s default setting 3 10s 4 15s 5 20s Stabilize for 1 Press zone key 1 This takes you to the System Config menu 4 Press zone key 4 This takes you to the Zone Reset submenu 2 Press zone key 2 This takes you to the Stabilize For submenu 5 1 Press zone keys 1 to 5 1 1s 2 5s default setting 3 10s 4 15s 5 20s 36 en System Configuration Conventional Fire Panel 2014 06 7 0 F 01U 172 980 Bosch Sicherh...

Page 37: ...s zone key 1 This takes you to the System Config menu 5 Press zone key 5 This takes you to the Aux Power submenu 3 1 Press zone keys 1 to 3 1 With Zone default setting 2 With Panel 3 Never Faults The Faults setting specifies whether faults on the fire panel are to be displayed until the fire panel is manually reset Notice This setting does not apply to system faults System faults can only be reset...

Page 38: ...4 characters long and is displayed during entry Notice The following codes are programmed in delivery status Operating level 2 1234 Operating level 3 3333 1 Press zone key 1 This takes you to the System Config menu 7 Press zone key 7 This takes you to the Code submenu 2 1 1 Level 2 Code 2 Level 3 Code 1 2 3 4 5 6 7 8 Level 2 Code Set to ____ You are prompted to enter the new code 4 1 7 38 en Syste...

Page 39: ...st History 1 Press zone key 1 This takes you to the System Config menu 8 Press zone key 8 This takes you to the Test History submenu 2 1 Use zone keys 1 or 2 1 Log Enabled default setting 2 Log Disabled Configuring Delays In the Delay Config menu you can program different delay times for different zone programs outputs and fault types 2 Press zone key 2 This takes you to the Delay Config menu 4 1 ...

Page 40: ...kes you to the Day Mode Off submenu 2 1 Use zone keys 1 or 2 1 Manual default setting 2 Automatic If you set Day Mode Off to Automatic you must program the changeover time from day to night mode 1 2 3 4 5 6 7 8 Off Time 17 00 Confirm with Set the time with the arrow keys and confirm using the ACK key Alarm Verification Notice This setting only applies to zones that are programmed as alarm verifica...

Page 41: ...acuate NAC 1 is switched off during the delay time and only activated during the actual alarm Time setting for alarm acknowledgement 2 Press zone key 2 This takes you to the Delay Config menu 2 Press zone key 2 This takes you to the Alarm Verific submenu 1 Press zone key 1 This takes you to the ACK Within submenu 4 1 Use the zone keys to set the respective delay 1 30 s 2 60 s default setting 3 90 ...

Page 42: ...Press zone key 3 This takes you to the NAC 1 submenu 2 1 Press zone key 1 or 2 1 Alert 2 Evacuate default setting Intermediate Alarm Storage Intermediate alarm storage is an automatic procedure designed to rule out false alarms as far as possible The entire procedure lasts up to 60 seconds Ten seconds after a fire is detected the zone is reset setting Reset After The zone is reset for x seconds se...

Page 43: ...e using automatic fire detectors find out from the manufacturer whether they can be used for intermediate alarm storage In this menu you can change the pre set time values indicated above Reset after 2 Press zone key 2 This takes you to the Delay Config menu 3 Press zone key 3 This takes you to the Int Alarm Stor submenu 1 Press zone key 1 This takes you to the Reset After submenu 4 1 Use the zone...

Page 44: ...ed If the fault is resolved before the time set here it is no longer displayed 2 Press zone key 2 This takes you to the Delay Config menu 4 Press zone key 4 This takes you to the Power Fault submenu 5 1 Use the zone keys to set the respective delay 1 No Delay default setting 2 1 min 3 5 min 4 10 min 5 15 min Zone Configuration In the Zone Config menu you can program the individual zones of the fir...

Page 45: ...e fire panel reverts to its normal state after 10 minutes Alarm verification Alarm Verific Notice Note that the delay is only effective in day mode In night mode the alarm is triggered immediately Notice If the fire panel automatically switches to night mode during an ongoing verification time an alarm is triggered immediately Notice If during the verification time in one zone an alarm is triggere...

Page 46: ... cannot be guaranteed Notice The fire panel does not support dual detector dependency with 4 wire detectors The zone must contain more than one detector If one of the detectors in the zone triggers this is evaluated as a pre alarm If an additional detector in the same zone is activated an alarm is triggered The panel automatically attempts to reset the pre alarm every 10 minutes However this is no...

Page 47: ...to program the zone 1 No Delay default setting 2 Int Alarm Stor 3 Alarm Verific 4 2 Det Depend 5 2 Zone Depend Zones 2 to 8 are pre programmed in the same way as zone 1 You can change the settings as with zone 1 Notice Zones 3 and 4 are only available on the FPC 500 4 and FPC 500 8 panels Zones 5 8 are only available on the FPC 500 8 Configuring Inputs In the Input Config menu you can program the ...

Page 48: ...menu Input 1 4 Press zone key 4 This takes you to the Input Config menu 1 Press zone key 1 This takes you to the Input 1 submenu 7 1 Use the zone keys to set the programming for input 1 1 Not Used default setting 2 Drill Evacuate 3 Silence 4 Level 2 5 Reset Panel 6 Ext PS Fault 7 Ext Batt Fault Notice You do not have to confirm the input functions on the panel Thus use a key switch if possible to ...

Page 49: ...appliances to particular zones Reactive NAC specifies whether silenced notification appliances are reactivated by a new alarm in another zone You can use NAC in test to specify whether the notification appliances are activated for 15 seconds when a zone test is performed Caution When assigning the zones to notification appliances make sure that each zone of the fire panel is assigned to at least o...

Page 50: ...ain the selection is cancelled ACK Confirm your selection Notification appliance 2 zone assignment See Notification appliance 1 zone assignment Notification appliance 1 zone assignment page 50 Reactivating notification appliances 5 Press zone key 5 This takes you to the Output Config menu 1 Press zone key 1 This takes you to the NAC submenu 3 Press zone key 3 This takes you to the Reactive NAC sub...

Page 51: ... Silencable and Drillable settings You can use Silencable to specify whether the relay can be silenced manually Drillable specifies whether the alarm relay is also activated during a manual alarm Drill Evac Alarm relay can be muted 5 Press zone key 5 This takes you to the Output Config menu 2 Press zone key 2 This takes you to the Alarm Relay submenu 1 Press zone key 1 This takes you to the Silenc...

Page 52: ...the zone triggers an alarm Here zone 1 is assigned to output 1 etc Zone Normal If the zone is not in a normal state the output is activated Assignment zone 1 to output 1 etc Sum Alarm When the fire panel is in an alarm state this output is activated regardless of the zone Sum PreAlarm When the fire panel is in a pre alarm state this output is activated regardless of the zone Sum Fault This output ...

Page 53: ...Test 8 Not Used The procedure for OC Relay 2 to 8 is the same Displaying the Configuration In the View Config menu you can display the programming of the fire panel 6 Press zone key 6 This takes you to the View Config menu i Use arrow keys to scroll more quickly through the displayed programming Hold the arrow key down to scroll through the menu in increments of 10 steps RESET To exit the display ...

Page 54: ...u to the NAC 1 submenu ACK RESET Press the ACK key Notification appliance 1 is activated Press the RESET key Notification appliance 1 is deactivated Notification appliance 2 7 Press zone key 7 This takes you to the Output Control menu 2 Press zone key 2 This takes you to the NAC 2 submenu ACK RESET Press the ACK key Notification appliance 2 is activated Press the RESET key Notification appliance 2...

Page 55: ...his takes you to the Output Control menu 4 Press zone key 4 This takes you to the Fault Relay submenu ACK RESET Press the ACK key The fault relay is activated Press the RESET key The fault relay is deactivated OC Relay Extension 7 Press zone key 7 This takes you to the Output Control menu 5 Press zone key 5 This takes you to the OC Relay Ext submenu 4 7 3 4 7 4 4 7 5 Conventional Fire Panel System...

Page 56: ... This takes you to the All submenu ACK RESET Press the ACK key All outputs are activated Press the RESET key All outputs are deactivated Resetting To Delivery State You can use Config Reset to reset the programming of the fire panel to the default values set when delivered Notice Resetting the fire panel deletes all of your changes to the programming The panel is reset to the default programming s...

Page 57: ...eset menu ACK RESET Press the ACK key The fire panel is reset to the delivery state Press the RESET key You exit the menu without making changes Conventional Fire Panel System Configuration en 57 Bosch Sicherheitssysteme GmbH 2014 06 7 0 F 01U 172 980 ...

Page 58: ... monitoring There is a thermal fuse on the motherboard that monitors the battery current and protects against reverse polarity When the fuse cools off the battery current is switched on again Updating the panel software firmware via USB You can update the panel software using the USB port on the lower left side of the main board To do this connect the USB port to your computer and install the prog...

Page 59: ...ns 0 1 2 Prog inputs 1 2 AUX output 1 Alarm device output 2 Relay 2 Electrical Data FPC 500 2 FPC 500 4 FPC 500 8 Power supply voltage 230 VAC 10 15 50 60 Hz Current consumption 275 mA 312 mA 375 mA AC power consumption 80 W Operating voltage 21 4 VDC to 29 VDC Imin 70 mA Imax a 0 7 A Imax b 2 3 A 6 6 1 Conventional Fire Panel Technical Data en 59 Bosch Sicherheitssysteme GmbH 2014 06 7 0 F 01U 17...

Page 60: ...C 500 mA 10 per output 22 5 Ohm 0 75 A 60 V Relay outputs Breaking capacity Max line resistance 1 A 30 VDC 22 5 Ohm Transistor outputs Breaking capacity Max line resistance No inductive loads 20 mA 24 VDC 22 5 Ohm Recommended cable type Unshielded cable 0 8 mm cable diameter cable cross section up to 1 5 mm2 Batteries Max inner resistance Max current consumption Fuse 800 mOhm 2 3 A 5 A 60 V End po...

Page 61: ...uts Alarm resistor 820 ohm 5 EOL Resistor 3900 ohm 1 Zones with resistance combination Alarm resistor 820 ohm 5 910 ohm 5 No 2 Det Depend 680 ohm 5 EOL Resistor 3900 ohm 1 Zones with EOL modules Alarm resistor 820 ohm 5 910 ohm 5 No 2 Det Depend 680 ohm 5 6 1 1 Conventional Fire Panel Technical Data en 61 Bosch Sicherheitssysteme GmbH 2014 06 7 0 F 01U 172 980 ...

Page 62: ...PC 500 4 FPC 500 8 Protection category according to EN 60529 IP 30 Protection class as per EN 60950 II EMC interference immunity emissions EN 61000 6 3 EMC interference immunity EN 50130 4 Vibrations EN 60068 2 6 Permitted operating temperature 0 C to 40 C Permitted storage temperature 10 C to 55 C 14 F to 131 F Relative humidity Max 95 non condensing 6 2 6 3 62 en Technical Data Conventional Fire...

Page 63: ... VAC 10 15 50 60 Hz Operating voltage 26 VDC to 29 VDC 3 Communication parameters None 4 Fuse values 3 15 A 250 V 5 Batteries 2 x 7 0 7 2 Ah max lead gel battery 6 Max current consumption 2 3 A 7 Max battery inner resistance 800 mOhm 8 Imin 70 mA Imax a 0 7 A Imax b 2 3 A 9 Cable parameters Battery Cable enclosed Board power supply Wired ex works 230 V power supply 1 5 mm2 standard cable 6 4 Conve...

Page 64: ...peration is required f Have maintenance and installation work carried out regularly by trained qualified personnel Bosch Sicherheitssysteme GmbH recommends carrying out a functional and visual check at least once a year Replace the batteries on a regular basis Please observe the appropriate requirements stipulated by the local authorities etc Options with requirements as per EN 54 2 1997 A1 2006 T...

Page 65: ... PreAlarm 2 History 1 Event History 2 Test History 3 Alarm Counter 4 System Info 1 SW Release 2 Operation Days Menu operating level 2 code required i 5 View Config 6 System Config 1 Date Time 2 Keypad Tone 1 On 2 Off 3 Language 1 1 A L 2 2 M Z 7 7 1 Conventional Fire Panel Appendix en 65 Bosch Sicherheitssysteme GmbH 2014 06 7 0 F 01U 172 980 ...

Page 66: ... 5 Zone 5 6 Zone 6 7 Zone 7 8 Zone 8 3 Dis Enable 1 Zones 1 Zone 1 2 Zone 2 3 Zone 3 4 Zone 4 5 Zone 5 6 Zone 6 7 Zone 7 8 Zone 8 2 NAC ACK YES ESC No 3 Relays ACK YES ESC No 4 All ACK YES ESC No 7 2 66 en Appendix Conventional Fire Panel 2014 06 7 0 F 01U 172 980 Bosch Sicherheitssysteme GmbH ...

Page 67: ...s 1 Resistor 2 Only 2W Module 3 With 4W Module 4 Zone Reset 1 Cut For 1 1 s 2 5 s 3 10 s 4 15 s 5 20 s 2 Stabilize For 1 1 s 2 5 s 3 10 s 4 15 s 5 20 s 5 Aux Power 1 With Zone 2 With Panel 3 Never 6 Faults 1 Latching 7 3 Conventional Fire Panel Appendix en 67 Bosch Sicherheitssysteme GmbH 2014 06 7 0 F 01U 172 980 ...

Page 68: ...nfig 2 1 Day Mode Off 1 Manual 2 Automatic Off Time 17 00 2 Alarm Verific 1 ACK Within 1 30 s 2 60 s 3 90 s 4 120 s 2 Invest Time 1 1 min Delay 2 2 min Delay 3 3 min Delay 4 4 min Delay 5 5 min Delay 6 6 min Delay 7 7 min Delay 8 8 min Delay 68 en Appendix Conventional Fire Panel 2014 06 7 0 F 01U 172 980 Bosch Sicherheitssysteme GmbH ...

Page 69: ...elay 4 Power Fault 1 No Delay 2 1 min Delay 3 5 min Delay 4 10 min Delay 5 15 min Delay Submenu 1 2 3 3 Zone Config 3 1 Zone 1 1 No Delay 2 Int Alarm Stor 3 Alarm Verific 4 2 Det Depend 5 2 Zone Depend 2 Zone 2 1 No Delay Conventional Fire Panel Appendix en 69 Bosch Sicherheitssysteme GmbH 2014 06 7 0 F 01U 172 980 ...

Page 70: ...lay FPC 500 8 4 Input Config 4 1 Input 1 1 Not Used 2 Drill Evacuate 3 Silence 4 Level 2 5 Reset Panel 6 Ext PS Fault 7 Ext Batt Fault 2 Input 2 See Input 1 FPC 500 8 Submenu 1 2 3 5 Output Config 5 1 NAC 1 NAC Zones 1 2 NAC Zones 2 3 Reactive NAC 1 By Other Zone 2 No Reactivate 70 en Appendix Conventional Fire Panel 2014 06 7 0 F 01U 172 980 Bosch Sicherheitssysteme GmbH ...

Page 71: ...ne Alarm 2 Zone Normal 3 Sum Alarm 4 Sum PreAlarm 5 Sum Fault 6 Sum Disable 7 Sum Test 8 Not Used 2 OC Relay See OC Relay 1 3 OC Relay See OC Relay 1 4 OC Relay See OC Relay 1 5 OC Relay See OC Relay 1 6 OC Relay See OC Relay 1 7 OC Relay See OC Relay 1 8 OC Relay See OC Relay 1 6 View Config Conventional Fire Panel Appendix en 71 Bosch Sicherheitssysteme GmbH 2014 06 7 0 F 01U 172 980 ...

Page 72: ... 4 OC Relay 4 ACK On ESC Off 5 OC Relay 5 ACK On ESC Off 6 OC Relay 6 ACK On ESC Off 7 OC Relay 7 ACK On ESC Off 8 OC Relay 8 ACK On ESC Off 6 All ACK On ESC Off 8 Config Reset Navigation in the menu i Press the arrow key to scroll up in the menu Press the arrow key to scroll down in the menu ACK Press the ACK key to confirm your selection 72 en Appendix Conventional Fire Panel 2014 06 7 0 F 01U 1...

Page 73: ...SET ESC Hold the ESC key down for 2 seconds to jump to the uppermost menu level 8 1 In the menu each menu item has a number from 1 to 8 preceding it Use the zone keys to select the desired menu item in the menu Conventional Fire Panel Appendix en 73 Bosch Sicherheitssysteme GmbH 2014 06 7 0 F 01U 172 980 ...

Page 74: ... Zone 6 Faults Latching 8 Test History Log Enabled 2 Delay Config 1 Day Mode Off Manual 2 Alarm Verific 1 ACK Within 60 s 2 Invest Time 1 min 3 NAC 1 Evacuate 3 Int Alarm Stor 1 Reset After 10 s 4 Power Fault No Delay 3 Zone Config 1 Zone 1 No Delay 4 Input Config 7 4 74 en Appendix Conventional Fire Panel 2014 06 7 0 F 01U 172 980 Bosch Sicherheitssysteme GmbH ...

Page 75: ...ones 2 NAC Zones All zones 3 Reactive NAC By Other Zone 4 NAC in test No Activation 2 Alarm Relay 1 Silencable Not Silencable 2 Drillable Not Drillable 3 OC Relay Ext 1 OC Relay 1 Zone Alarm Conventional Fire Panel Appendix en 75 Bosch Sicherheitssysteme GmbH 2014 06 7 0 F 01U 172 980 ...

Page 76: ...nabled Input Open Input interrupted Input Short Input short circuit Input Normal Input normal Aux Power Short Short circuit in the AUX power supply Aux Power Normal Error in the AUX power supply eliminated NAC Open Notification appliance line interrupted NAC Short Notification appliance short circuit on line NAC Normal Notification appliance normal Fault was eliminated NAC Enabled Notification app...

Page 77: ... Ext BATT Normal Fault in external battery resolved Sys Load Fault Current consumption of panel and all connected peripherals is above 3 5 A Sys Load Normal Current consumption is back in permitted range System Fault System fault Panel boot up Panel has been restarted Reset Panel Panel has been reset Night Mode Panel has switched to night mode Day Mode Panel has switched to day mode Earth Fault Gr...

Page 78: ...lenced alarm has been reactivated Test Memory Messages Message Meaning Zone Start Zone set to test mode Zone Test Zone successfully tested Zone End Zone test mode exited 7 6 78 en Appendix Conventional Fire Panel 2014 06 7 0 F 01U 172 980 Bosch Sicherheitssysteme GmbH ...

Page 79: ... E Emergency power supply Batteries 17 Extensions 18 F Fault handling Store faults 37 H Housing Installing 15 Open 14 I Input 20 Programming a function 48 Installation location 13 Intermediate alarm storage Setting 42 Invest time Setting 41 M Mains supply 16 N Navigating Arrow keys 33 Navigation 72 Zone keys 33 73 Notification appliance 24 Assignment to zones 50 Behavior in zone test 51 Specifying...

Page 80: ...nce Terminal element EOL module End Of Line module 20 21 Test log Setting 39 Z Zone reset Disconnection duration 36 Setting times 35 Stabilization time 36 Zone termination Setting 35 Zone types 44 dual detector dependency dual detector dependency 46 Dual zone dependency dual zone dependency 46 Intermediate alarm storage Intermediate alarm storage 45 Manual alarm verification Manual alarm verificat...

Page 81: ......

Page 82: ...Bosch Sicherheitssysteme GmbH Robert Bosch Ring 5 85630 Grasbrunn Germany www boschsecurity com Bosch Sicherheitssysteme GmbH 2014 ...

Reviews: