FPP-RNAC-8A-4C
|
Operation and Installation Guide | 4.0
DIP Switch and Option Bus Settings
18
Bosch Security Systems, Inc. | 8/09 | F01U025431-02
4.2 Switch
S2
Use Switch S2 to set the following (refer to
Table 8
):
•
NAC output control
•
AC failure delay time – 0, 1, 3, and 6 hour delay
•
Option bus address – Bus Addresses 1 to 14
Table 8: DIP Switch S2 Settings
Position Name
CNTRL
ALL/
CNTRL 2
AC
DELAY 1
AC
DELAY 0
OPTION
ADDRESS 4
OPTION
ADDRESS 3
OPTION
ADDRESS 2
OPTION
ADDRESS 1
Position Number
0
1
2
3
4
5
6
NAC Output Control Options
NAC Input 1 controls
NAC Outputs 1 and 2.
NAC Input 2 controls
NAC Outputs 3 and 4.
OFF
NAC Input 1 controls all
four NAC Outputs
ON
AC Failure Delay Reporting Options
No delay
in AC failure reporting; the
unit signals an AC Failure
immediately.
OFF
OFF
AC failure reporting delay =
1 hour
.
OFF
ON
AC failure reporting delay =
3 hours
ON
OFF
AC failure reporting delay =
6 hours
ON
ON
Option Bus Settings
Disabled
OFF
OFF
OFF
OFF
Address
1
OFF OFF OFF ON
Address 2
OFF
OFF
ON
OFF
Address
3
OFF OFF ON ON
Address 4
OFF
ON
OFF
OFF
Address
5
OFF ON OFF ON
Address 6
OFF
ON
ON
OFF
Address
7 OFF ON ON ON
Address 8
ON
OFF
OFF
OFF
Address
9
ON OFF OFF ON
Address 10
ON
OFF
ON
OFF
Address
11 ON OFF ON ON
Address 12
ON
ON
OFF
OFF
Address
13 ON ON OFF ON
Address 14
ON
ON
ON
OFF
Address 15
Reserved