FPP-RNAC-8A-4C
|
Operation and Installation Guide | 4.0
DIP Switch and Option Bus Settings
20
Bosch Security Systems, Inc. | 8/09 | F01U025431-02
4.4
Option Bus Address
To activate a new address, remove the
AC and battery power from the
FPP-RNAC-8A-4C. Wait 60 sec. Restore
the power after it is removed. The new
address becomes active after power is
restored to the FPP-RNAC-8A-4C.
The FPP-RNAC-8A-4C needs its own address
(1 to 14) when using the option bus connection. Use
Switch S2, Positions 3 through 6.
Refer to
Figure 13
on page 22 for the correct DIP
switch positions.
4.5
NAC Input Variable
Instead of having Input 1 drive NAC Output 1 and 2
and Input 2 drive NAC Output 3 and 4, Input 1 can be
set to drive all four outputs. Set Switch S1 to the ON
position to select this option.
4.6
AC Fail Time Delay
A trouble condition is registered to the control panel
but is not indicated with an LED if the AC falls below
85/105V for more than 5 sec. A programmable time
delay allows the indication of AC failure to be delayed
by 0, 1, 3, or 6 hr. The default value is 0 hr.
Use Switch S2 positions 1 and 2 for these settings.
UL864 requires that off-premises
signaling of AC Trouble is delayed
between 60 and 180 minutes.
To comply with this requirement:
•
Set the AC Fail Time Delay to 0, and
•
Program the FACP to delay the off-
premises AC Trouble signal to a
value between 60 min and 180 min.