FPP-RNAC-8A-4C
|
Operation and Installation Guide | 6.0
Specifications
24
Bosch Security Systems, Inc. | 8/09 | F01U025431-02
Table 11: Specifications (continued)
Trouble Relay Output
Contact Type
Form C
Contact Rating
1.5 A, 30 VDC resistive load
AC Trouble Relay Output
Contact Type
Form C
Contact Rating
1.5 A, 30 VDC resistive load
Power Output Circuit when Notification Appliance Circuit (NAC) is Configured as a Power Output Circuit
Output Voltage
24 VDC Nominal
Range for Compatibility
19.6 to 27.5 VDC
Output Current
1.3 A maximum
Ripple Voltage
250 mVpp
Maximum current of 8 A is shared among all notification appliance circuits (NAC), power output circuits, and
auxiliary power circuit. Power Limited, Special Application.