Menu settings INSTALLER SETTINGS (for contractors only)
8.4 Configuring the solar thermal
system
Contractor level: Solar system config
Use this menu if you want to set the thermal
disinfection function for the solar thermal
system.
•
Solar sys option E Thermal disinfection
for
thermal disinfection
For menu structure and setting ranges
Æ
page 55.
8.5 Parameters for solar thermal
system
Contractor level: Solar sys parameters
The default parameter settings on this menu are
suitable for many common system dimensions.
Use this menu if you want to finely adjust the
parameters to suit the installed solar thermal
system.
•
PE: Therm disinfect pump mode
: Use this
menu point to select the pump (PE) mode for
thermal disinfection.
–
Auto
: Automatically controlled operation
according to the set parameters.
–
Manual On
: Switches the pump
permanently on (e.g. for function test
when commissioning).
–
Manual Off
: Switches the pump
permanently off (e.g. for servicing work on
the pump without having to interrupt
heating operation).
For menu structure and setting ranges
Æ
page 56.
The heating system's solar thermal
system has to be configured
manually. Automatic configuration of
the heating system (
Æ
chapter 8.2,
page 58) does not configure the
solar thermal system.
An example system is shown in
chapter 8.2 on page 58. Other
examples can be found in the
instructions for the ISM or the
technical guides.
Fill and vent the solar thermal
system according to its
documentation and prepare it for
commissioning as described this
chapter.
The designations of the pumps and
the temperature sensors, e.g. (PE)
or (T1), are also used in the ISM
installation instructions.