Menu settings INSTALLER SETTINGS (for contractors only)
8.5.3 Parameters for solar optimisation
Solar optimisation is performed automatically
according to the available solar output.
Calculation of the solar output requires
specification of the installed collector area, the
collector type and the climate zone in which the
system is installed.
Menu: Solar sys parameters > Solar
optimisation
Use this menu to set the parameters for solar
optimisation.
•
Collector group 1 area
: Use this menu point
to set the installed collector area for collector
group 1.
•
Collector group 1 type
: Use this menu point
to set the installed collector type for collector
group 1.
•
Climate zone
: Use this menu point to set the
climate zone number for the geographical
region in which the system is located.
–
Find the location of your system on the
climate zones map (
Æ
Fig. 16) and enter
the climate zone number.
–
If your location is not shown on the map, leave
the number as it is (factory setting is 90).
•
Optimizing influence DHW
: This parameter
can also be set on on the main menu under
Solar
. A detailed description can be found on
page 50.
For menu structure and setting ranges
Æ
page 56.
Collector
type
Gross areaper collector in
m
2
FK 210
2.1
FK 240
2.4
FK 260
2.6
VK 180
1.8
FKT-1
2.4
FKC-1
2.4
FKB-1
2.4
Tab. 8
Gross collector areas