7 2 |
Bosch Greenstar
Applications Manual
Bosch Thermotechnology Corp.
Data subject to change
120 VAC
24 VAC
L
N
red
storage
tank pump
L
N
black
ch pump
for unmixed heating
L
N
white
mains
120v/60 hz
Ground
Neutral
120 V
Transformer
External Junction
Box on back of
Greenstar Floor
boiler
Low Voltage Junction
Box on back of floor
boiler
Hydrolevel Safgard 1100
Low Water Cut-Off
Ź
Install a 24VAC 20VA Transformer near the boiler
Ź
Follow LWCO manufacturer’s instructions
Ź
Connect the lead labeled BOILER GROUND (green) to the ground wire of the white plug in the boiler
junction box
Ź
Connect the leads labeled 24V HOT(red) and 24V COMMON(white) to the external 24VAC transformer
(field supplied)
Ź
AT the Low Voltage box on the rear of the boiler, remove the jumper acros the LWCO connections and
connect the leads labeled SWITCH CONTACT (yellow) to these connections.
Appendix E: Wiring Hydrolevel safgard 1100 Low Water Cut-Of
to Greenstar Floor Boiler
Main Power
Supply
Yellow
Yellow
Green
White
Red
BUS
TT
out sen
LWCO
DHW sen
1
2
3
4
5
6