The standard 100mm diameter horizontal flue system is suitable
for lengths upto 2m.
Flues upto 670mm do not require an extension duct assembly.
Flues between 670mm 1620mm require 1 extension duct
assembly.
Flues between 1620mm and 2000mm require 2 extension duct
assemblies.
NOTE: Flue lengths between 670mm and 730mm cannot be
accomodated.
Refer to Fig.F1,F2 and F3.
Standard system comprise:
Flue turret
_
Flue turret clamp
_
Terminal assembly
_
Wall sealing
plates.
Extension kit comprises:
Air duct
_
Flue duct
_
Duct clamp.
Refer to Fig.F4.
10
12. Installation
Fig. F1. Standard Flue.
Flue
Turret
Flue
Sample
Point
Clamp
No
Clamp
Maximum 670mm
Terminal
Assembly
Outer
Wall
Fig. F2. Flue with One Extension .
Maximum 1620mm
Flue
Turret
Flue
Sample
Point
Clamp
No
Clamp
Clamp
Terminal
Assembly
Outer
Wall
Extension
Duct
Fig. F3. Flue with Two Extensions .
Flue
Turret
Flue
Sample
Point
Clamp
No
Clamp
Maximum 2000mm
Clamp
Extension
Duct
Clamp
Extension
Duct
Terminal
Assembly
Outer
Wall