background image

Connect a drain to the relief valve outlet ensuring that it does not
discharge onto electric components or where it might be a
hazzard. The pipe must be not less than 15mm in diameter.

Make the electrical connections to the appliance through the
cable clamps in the base of the appliance.

Remove the drop-down facia cover by lowering it to the
horizontal position and pushing firmly upwards at the rear
supports to release the cover. Lift the cover from the appliance.
Remove the clipped on-cover and unscrew the inner cover to
expose the connectors. Refer to Fig.16. 

Remove the automatic air vent cap. See Fig. 14. 
Check that all the gas and water connections on the manifold are
tight.

Final Installation.
Replace the cabinet front panel.
Refer to Section 13 Commissioning, for a full discription of the
filling, venting and pressurisation  of the system.

If the appliance is not to be commissioned immediately then
check that the gas supply, the electrical supply  and all the water
connections are turned off.

If the premises are to be left unoccupied in very frosty conditions
then drain any water from the appliance and the system   

Test the gas supply for soundness as described in BS 6891.

If  the appliance is not to be commissioned immediately replace
the cabinet. Turn off the gas, electrical and water connections. 

The appliance is adjusted at the factory to give the settings
shown in table 7.
If any changes are made to these settings they must be recorded
on the commissioning label to be fixed to the appliance and in
the relevant booklet.
The domestic hot water discharge temperature and the central
heating flow temperature may be adjusted on the facia to satisfy
different conditions.

Domestic Hot Water
Confirm that the mains water supply has been flushed out at
installation. If not it will be necessary to disconnect the cold
water inlet pipe at the appliance and thoroughly flush.

Central Heating
Confirm that the central heating system has been fully
flushed out at installation. If not then thoroughly flush the
system using clean water if possible. Any additives must be
compatible with aluminium heat exchangers.

The system water must not have a pH greater than 8 or the
appliance guarantee will be rendered invalid. If any system water
treatment is required then only products suitable for use with
Aluminium shall be used i.e. Fernox-Copal or Sentinel X100, in
accordance with the manufacturers instructions. The use of any
other substances will invalidate the guarantee.

Gas Service

The complete system, including the meter, must be inspected
and tested for soundness and purged as described in BS 6891.
Check that the gas and electrical supplies to the appliance are
turned off.

Check that any controls are in the off position.
Check that all the water connections throughout the system are
tight.

Remove the cabinet by unclipping the two clips and lifting away.
Refer to Fig.12.
Remove the automatic air vent caps. Refer to Fig.14.

Open the heating system valves on the manifold and all the
radiator valves. Fill the system through the WRc approved filing
connection to a pressure of about 1.5 bar and check for water
soundness. Refer to Fig.6 and 7. The automatic air vents on the
appliance will remove air from the appliance but each radiator
must be vented separately. The manual air vent must be open to
allow the venting of the appliance. Tighten the screw when
venting is complete. Refer to Fig.15.

Fill the condensate trap by opening the manual air vent/siphon
fill  connection until water is discharged showing that the siphon
is full. Refer to Fig.15.

Check that the pressure relief valve operates by, after removing
the cap, turning the knob anti-clockwise until it releases and
water is expelled from the discharge pipe. The relief  valve is
located beneath and behind the pump at the right-hand side.

Remove the plated cap from the pump and turn the shaft about
half a turn using a flat blade screwdriver. Replace the cap. Refer
to Fig.15.

Set the system pressure to 1bar by releasing water from the relief
valve and, if necessary, the expansion vessel pressure.
The 10 L expansion vessel, supplied with a charge pressure of
0.75 bar (static head 7.5 metres), must not be at a pressure less
than the static head of the system. A schraeider type valve is
provided on top of the vessel if it is necessary to increase the
charge pressure.
Refer to BS7074:1 and Table 9 for details of the allowable system
capacity.
If the system volume is greater than that which can be
accomodated by the expansion vessel on the appliance then an
extra vessel must be fitted as close to the appliance as possible
in the central heating return. It must be charged to the same
pressure as the vessel in the appliance.

Connect a pressure gauge to the gas valve inlet pressure test
point and open the gas tap. See Fig. 19.

Set all the external system controls to on or maximum. 
Set the central heating and domestic hot water control knobs to
minimum. Check that the condensate trap and syphon are full
(to prevent flue gas spillage).

The appliance must NOT be operated without the siphon
being full.

The instructions following describe the operation of the
appliance.

13. Commissioning

15

Summary of Contents for Greenstar ZWBR 11-25 A31

Page 1: ...Greenstar ZWBR 11 25 A31 L P G 47 311 45 THIS APPLIANCE IS FOR USE ON SEALED PRIMARY SYSTEMS ONLY IMPORTANT THESE INSTRUCTIONS APPLY IN THE UK ONLY THESE INSTRUCTIONS ARE TO BE LEFT WITH THE USER OR AT THE GAS METER This appliance must be installed by a competent person in accordance with the Gas Safety Installation and Use Regulations 1998 Cat II appliance 2H 3P S S u p p e m e m m ...

Page 2: ... in a cupboard or compartment Do not block the specified space left for servicing An electrical supply failure will stop the appliance Normal operation will resume upon the restoration of the supply A standard 100mm flue system is available for horizontal flues upto 2m Multi directional flue systems are available up to 10m horizontally and 8m vertically A twin pipe system is available An integral ...

Page 3: ...URE C TEMPERATURE C kW kW Net m3 h MAXIMUM 80 60 23 0 24 0 2 54 50 30 25 3 24 0 2 54 MINIMUM 80 60 6 7 7 2 0 762 50 30 7 7 7 2 0 762 Table 1 3 Technical Data Fig 1 Appliance water flow diagram Automatic Air Vent Water to Water Heat Exchanger Automatic Air Vent Charging Point Expansion Vessel Heat Exchanger Condensate Trap Drain Diverter Valve Flow Switch Siphon Drain Pump Pressure Relief Valve Dom...

Page 4: ...5 C 9 5 Rate l min Temperature Rise 40 C 8 4 Maximum Mains Pressure bar 8 0 Minimum Mains Pressure bar 0 2 Table 10 Factory Setting Pump Control Mode 2 Anti Cycle Time min 3 Maximum CH Temperature C 80 ThermostatTemperature Differential C 8 Maximum CH Output kw 23 0 standard 25 3 condensing Minimum CH Output kw 6 7 standard 7 7 condensing Table 7 HORIZONTAL 100mm Overall Diameter of Duct mm 100 Fl...

Page 5: ... the appliance after installation The only flue systems that may be used are those sold by Worcester Heat Systems The flue system must be installed in accordance with the requirements of BS5440 1 Standard 100mm flue system The standard concentric flue system provides for a horizontal length of upto 2m Full instructions for fitting this flue are in Section 12 Installation Alternative 125mm diameter...

Page 6: ...he meter governor should deliver a dynamic pressure of 20 mbar at the appliance equivalent to a pressure of about 18 5 19mbar at the gas valve inlet 7 Gas Supply 6 Siting the Flue Terminal L L K K F F G A M E J F HI D G A B C 6 Fig 5 Acceptable terminal positions TERMINAL POSITION MIN DISTANCE A Directly below an openable window or other opening e g air brick 300 mm 12 in B Below gutters soil pipe...

Page 7: ...cal water company All connections in the system must be capable of withstanding a pressure of up to 3 bar and the radiator valves conform to the requirements of BS 2767 10 If Thermostatic Radiator Valves are fitted then it is recommended that one radiator is left open Repeated venting probably indicates a leak and this must be rectified to ensure the proper operation of the appliance No galvanised...

Page 8: ... appliance provided that it is in accordance with the requirements of the local water company The outlet s should be shrouded and unable to have any temporary hand held spray attached No anti syphonage arrangements are necessary In exceptionally hard water areas a device to prevent scale formation may be fitted or alternatively the maximum temperature reset to about 45 C which may reduce the risk ...

Page 9: ...0 DHW temperature control 11 Power on indicator 12 Ignition transformer 13 Ignition electrodes 14 Setting button 15 Reset button 16 Display 17 Service button 18 ECO button 19 Burner indicator 20 DHW temperature sensor 21 Water pressure switch flow switch 22 DHW inlet sensor 23 Air flow switch 24 CH flow temperature sensor 25 Flame sense electrode 26 Gas valve 27 Gas solenoid valve No 1 28 Gas sole...

Page 10: ...ise Flue turret _ Flue turret clamp _ Terminal assembly _ Wall sealing plates Extension kit comprises Air duct _ Flue duct _ Duct clamp Refer to Fig F4 10 12 Installation Fig F1 Standard Flue Flue Turret Flue Sample Point Clamp No Clamp Maximum 670mm Terminal Assembly Outer Wall Fig F2 Flue with One Extension Maximum 1620mm Flue Turret Flue Sample Point Clamp No Clamp Clamp Terminal Assembly Outer...

Page 11: ... supplied to secure the top and bottom cross members Refer to Fig 9 Ensure that the top section has the support lugs facing upwards and outwards 11 Fig 9 Wall mounting assembly Fig 11 Manifold connections Central heating flow Valve clips Wall mounting manifold plate Domestic hot water Cold water inlet Central heating return Gas 30 20 10 200 65 65 65 65 Support Lugs Manifold Assembly Wall Mounting ...

Page 12: ...t Red Leads Heat Exchanger CH Return Flue Temperature Thermostat Red Leads Air Flow Switch Gas Control Module Gas Air Mixing Tube Expansion Vessel Automatc Air Vent Expansion Vessel Cap Automatic Air Vent Heat Exchanger Cap Fig 12 Removal of casing Casing Security Screw remove Casing Clip 2 Syphon Syphon Drain Pipe Drain Manifold Assembly Expansion Vessel Connection Expansion Vessel Fixing Screws ...

Page 13: ...m the flue terminal The diameter of the hole required for the alternative flue system can be found in the instructions sent with the flue kit The heating system and the domestic water pipes can now be connected if not already done so Do not fix the pipes rigidly to the wall as some movement of them must be retained A flexible link is provided to allow the flushing of the system NOTE The domestic w...

Page 14: ... at the terminal indicating the outer face of the wall Refer to Fig F7 Extension air duct L 70mm flue duct L 50mm The measurement is from the formed end Assemble flue system completely Push the ducts fully together and clamp in the positions shown in Fig 2 and 3 The slope of the terminal outlet must face downwards The assembly will be made easier if a solvent free grease is lightly applied i e Vas...

Page 15: ...ee Gas Service The complete system including the meter must be inspected and tested for soundness and purged as described in BS 6891 Check that the gas and electrical supplies to the appliance are turned off Check that any controls are in the off position Check that all the water connections throughout the system are tight Remove the cabinet by unclipping the two clips and lifting away Refer to Fi...

Page 16: ...stem bypass If after conversion the appliance is operating on LPG then a dynamic pressure of 37mbar at the inlet to the appliance equivalent to aout 34 5 35mbar at the inlet to the gas valve Turn on the power switch to I The green LED will light NOTE The first time the appliance operates and whenever the electricity supply is re established it will run at low rate for 15 minutes to check the sipho...

Page 17: ...ost Protection Room Temperature Control Optional Junkers control Set the temperature control knob to the required setting Set the outside temperature control unit if fitted to the appropriate heating curve and mode Refer to the instructions sent with the controler NOTE A proprietary room thermostat can be connected Refer to Fig Turn the control knob to set the discharge temperature between 40 C Mi...

Page 18: ...r temperature control knob fully anti clockwise until the buttons flash 18 Changing the Maximum Heating Output Pump Anti Seizure Device If the pump has not operated for 24 hours then it will be switched on for a period of 5 minutes to prevent seizure The central heating flow temperature can be adjusted between 35 C and 80 C It can be set to give a maximum of 75 C i e setting E Prise off the yellow...

Page 19: ...h Press the service button until appears The maximum central heating flow temperature is stored Return the temperature control knobs to the original settings Record the change in the Commissioning Record Turn the hot water temperature control knob clockwise until the required output level is reached Display Heat Heating Output Level Input kw Output kw MAX NET Non condensing Mode 99 24 23 85 20 6 1...

Page 20: ...c hot water only Turn the central heating temperature control knob to E Press the service button until appears on the display Release the button 4 6 will appear for 5 seconds followed by 0 0 or 0 1 The service button will light 20 Changing the Control Mode for Heating Operation Turn the central heating temperature control anti clockwise until 2 2 appears after 5 seconds the mode setting of 2 facto...

Page 21: ... law that any service work is carried out by competent engineers such as British Gas or CORGI registered engineers Pre Service Inspection Check that the flue terminal and terminal guard are clear and undamaged If the appliance is in a cupboard compartment check that the specified service spaces are clear Refer to Fig 2 and 3 Check the connections in the system and remake any which show signs of le...

Page 22: ...Refer to the diagram and table below 22 Fig S2 Fig S3 Service Function How to read out Pump control mode 2 2 Anti Cycle time 2 4 Maximum heating flow 2 5 temperature Heating temperature 2 6 switching differential Maximum heating 5 0 output Press 1 and 2 until display 4 shows Wait until 4 shows 0 0 or 0 1 Press 1 and 2 until display 4 shows Wait until 4 shows 0 Turn 3 until display 4 shows 2 2 Wait...

Page 23: ... by unscrewing the two extended screws Unscrew the rear fixing screw remove the split pins and unscrew and remove the front fixings Remove burner casing Lift out the burner skin and seal Refer to Fig 20 Lightly brush the exposed flueways Remove the yellow siphon trap drain plug and the grey condensate drain cap Refer to Fig 31 Pour clean water through the heat exchanger and into the condensate tra...

Page 24: ... Lower to the horizontal position and push firmly upwards at the side location points to release Remove the panel b Cabinet Release the clips at the rear of each side of the appliance and lift off Refer to Fig 9 c Facia Assembly Unplug the spark and electrode connection Unscrew the screws at each end of the facia and lower assembly Refer to Fig 15 d Inner Case Cover Unscrew the four screws and rem...

Page 25: ...ce the control board and or transformer remove the cover panel Release the four clips to remove the control board and transformer Refer to Fig 14 Air Flow Switch Remove the Control Module Carefully pull off plastic tube to unclip the switch Carefully remove the assembly and remove the connectors Refer to Fig 14 Spark Electrode Remove the inner case cover Pull off the leads to the electrodes Unscre...

Page 26: ... and unscrew the insert from the body Refer to Fig 15 Refill vent and re pressurise the appliance Prime the siphon Expansion Vessel Drain the appliance Remove the inner case cover Remove the control module Release the union connection at the base of the expansion vessel Unscrew the two screws fixing the vessel Refer to Fig 14 In the unlikely event of a failure of the expansion vessel it is accepta...

Page 27: ...ct the union connections Refer to Fig 24 Unscrew the four screws securing the valve to the mounting plate and remove he valve by firmly pulling it from the connections Refill vent and re pressurise the appliance Prime the siphon Pump Drain the appliance Unplug the electrical connections at the facia Lower the facia and remove the cross brace Refer to Fig 15 and 24 Remove the plastic side facia pan...

Page 28: ... 1 8 729 000 2420 14 Expansion vessel 1 8 715 407 176 0 15 Relief valve 1 8 717 401 012 0 16 Spark electrode 1 8 718 107 064 0 17 Electrode lead 1 8 714 401 878 0 18 Flame Sense electrode 1 8 718 107 064 0 19 Pump 1 8 717 204 264 0 20 Pressure gauge 1 8 717 208 061 0 21 Inspection glass assembly 1 8 729 000 176 0 22 Sensor DHW flow temp 1 8 714 500 054 0 23 Burner skin seal 1 8 711 004 168 0 24 Tr...

Page 29: ...ding Display A5 A7 AC b1 C1 C4 C6 CC d3 E0 E2 E9 Condition Circuit break or short circuit in the constant hot water temperature sensor Circuit break or short circuit in the dhw temperature sensor No electrical connection between the controller TA211E and the control board Code plug Air pressure switch contacts open when appliance is operating or fan speed to slow Air pressure switch contacts do no...

Page 30: ...ame sense current remains after normal shut down i e burner does not go off Action Check that the gas cock is open and for sufficient gas pressure Check power to the gas valve Check spark and flame sense electrodes and leads Check electrode and lead for splits or cracks Check gas valve wiring and solenoids State 4 4 4 ...

Page 31: ...31 ...

Page 32: ...in the interests of continued improvement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application PUBLICATION 6 720 610 096 99 07 EXCELLENCE COMES AS STANDARD Worcester Heat Systems Limited Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 754619 Bosch Care Call 0990 266241 ...

Reviews: