54
|
Commissioning
Greenstar
6 720 806 992 (2015/03)
▶ Turn the dial
until
Design Temp
will be highlighted.
▶ Press the dial
.
168 °F
(75 °C) will fl ash. This is the supply temperature at 5 °F
( – 15 °C) outdoor temperature.
▶ Set accordingly (
Fig. 64).
▶ Press the dial
to confirm the setting.
Fig. 64
[1]
Maximum Base Line Adjustment 186 °F (85 °C)
[2]
Minimum Base Line Adjustment 50 °F (10 °C)
[3]
Maximum Design Temperature Adjustment 186 °F (85 °C)
[4]
Minimum Design Temperature Adjustment 86 °F (30 °C)
AT
Outdoor temperature
VL
Supply temperature
▶ Turn the dial
counter-clockwise until
Maximum heating supply
temperature
is highlighted.
▶ Press the dial
.
▶ Turn the dial
to set the desired value.
▶ Press the dial
to confirm the setting.
▶ Press menu button
to return to main display.
8.5.4
Adjusting warm weather shut down (WWSD)
▶ To open
INSTALLER SETTINGS
: press and hold the menu button
for approx. 5 seconds.
System configuration
will be highlighted.
▶ Turn the dial
one click counter-clockwise to highlight
Heating
parameters
.
▶ Press the dial
.
Heating circuit 1
will be highlighted.
▶ Turn the dial
counter-clockwise until
Heating OFF at outdoor
temperature
is highlighted.
▶ Press the dial
and the display will fl ash.
The default value is 68 °F (20 °C) and is adjustable from 50 °F (10 °C)
to 77 °F (25 °C). Turning above 77 °F (25 °C) will move it to 210 °F
(99 °C), which disables WWSD.
▶ Press the dial
to confirm the setting.
8.5.5
Resetting all settings (for installers only)
This function resets all settings on the
MAIN MENU
and the
INSTALLER
SETTINGS
to their factory settings.
Following such a reset, you will
need to commission the system again!
If the default display is showing:
▶ Simultaneously press and hold the menu button
and the delete
button
until a count down display appears.
▶ Continue holding the menu button
and the delete button
until the message appears that the reset is completed.
▶ Press .
All settings have now been reset to their factory settings with the
exception of the date and time, which remain unchanged.
8.6
After commissioning
▶ Check flue path for tightness.
▶ Check gas supply dynamic pressure (
page 67).
▶ Check that condensate is being discharged from the condensate
hose. If that is not the case, switch the appliance first OFF and then
ON again using the ON/OFF switch. That activates the trap filling
sequence (
page 62). Repeat the procedure several times until
condensate starts running out.
▶ Complete commissioning report (
page 81).
Refer to the FW 200 Installation and Operating
Instructions for more custom settings.
6 720 806 992-07.1O
68
50
32
14
- 4
68
86
104
122
140
158
176
194
1
3
4
2
50
VL
/ °F
AT / °F
20
10
0
- 10
- 20
20
30
40
50
60
70
80
90
10
VL
/ °C
AT / °C
menu
menu
menu
menu
Summary of Contents for Greenstar
Page 102: ...102 Index Greenstar 6 720 806 992 2015 03 ...
Page 103: ...Index 103 6 720 806 992 2015 03 Greenstar ...
Page 104: ......