- 19 -
Isolating a detector in a detector zone
Description
This function can be used to isolate individual
detectors before the system is armed. Areas
with isolated detector zones can be entered if
the system is armed, without an alarm being
triggered. Not in compliance with VdS.
Procedure
1. To call up "ISOLATE ZONES" from the
menu, see chapter "Calling up and ending
functions".
2. Call up detector zone.
By pressing the "ENTER" key, the first de-
tector zone that can be isolated and its
status (ON/OFF) will be displayed.
3. Call up additional detector zones.
By scrolling with the
keys or by direct
entry of the address using the number pad,
additional detectors zones that can be iso-
lated are displayed.
4. Search for "Detector".
Press center
key 2 x to enable the
display of individual detectors.
5. Call up detector.
By pressing the right
key, the first de-
tector from the selected detector zone will
be displayed.
6. Call up additional detectors.
By scrolling with the right
key, a par-
ticular detector from this detector zone can
be selected and displayed.
7. Initiate isolation procedure.
Once the detector zone to be switched off
has been called up, the isolation procedure
is initiated by pressing the center
key.
8. Isolate detector.
Press the right
key to isolate the de-
tector. After isolation has been completed,
the new status of the detector (=OFF) will
be displayed.
9. Reset
.
Press "STOP" key 2 x. The "STOP" key
causes a return by one level. The menu will
be displayed.
ZO 0002 = ON
v
ZO 0001 = ON
v
0002 – 13 = OFF
v
0002 – 13 = ON
ON v OFF
0002 – 13 = ON
v
ZO 0002 = ON
? v DETEC
06: ISOLATE ZONES
0002 – 01 = ON
v
06: ISOLATE ZONES
Operation in the menu
Summary of Contents for IUI-UEZ-BE1000s
Page 21: ... 21 Notes ...
Page 22: ... 22 Notes ...
Page 23: ... 23 Notes ...
Page 43: ... 43 Notizen ...
Page 44: ... 44 Notizen ...
Page 45: ... 45 Notizen ...
Page 65: ... 65 Remarques ...
Page 66: ... 66 Remarques ...
Page 67: ... 67 Remarques ...
Page 87: ... 87 Opmerkingen ...