Connection instructions
Type L 309
Power Supply Module
12
1070 078 131-104 (00.05) GB
5.4. Mains voltage selection
WARNING!
- Make sure that the mains voltage is set when the unit is safely isolated from
supply! Use suitable insulated tools!
If necessary, the customer himself may select the following voltages:
Types L 309.150 and L 309.250
:
- 400 V
jumper between X3/1 and X3/2
(state as delivered)
- 415-440 V
jumper between X3/1 and X3/3
- 500-550 V
jumper between X3/1 and X3/4
Type L 309.151
:
- 400 V
jumper between X3/1 and X3/2
- 460-480 V
jumper between X3/1 and X3/3
(state as delivered)
- 575 V
jumper between X3/1 and X3/4
X3/4
X3/3
X3/2
X3/1
!