FlexibleAutomation
Fault messages
Type L 309
Power Supply Module
19
1070 078 131-104 (00.05) GB
8. Fault messages
Extensive precautions were taken for protecting the thyristor block. These include,
i.a., the following
-
Temperature monitoring
A bimetallic switch is located at the thyristor block which transmits a message to
the timer unit when temperatures
56
_
C are reached. As a consequence, the
timer is inhibited - the ready signal at the timer goes off and the fault message
”Overtemperature - power supply fault” will be output.
Possible causes
Elimination
- not enough cooling water
check water inlet and outlet
- thyristor rating too small
calculate % duty cycle, check thyristor
dimensioning on the basis of the load
diagram (please refer to section
”Dimensioning instructions”).
-
Protective circuit against transient overvoltages
In order to prevent the thyristor from being destroyed by overvoltages, it is pro-
tected by an MOV (metal-oxide varistor). In the case of overvoltages in the
mains (e.g. due to spurious peaks or pulses), the MOV acts as a protective
diode, cutting off the peaks. As a result, fuse F4 (FF 6.3 A 500 V 6.3 x 32 mm)
might melt.
For replacement of fuses, please refer to ”Maintenance” section.
F3
F4
Summary of Contents for L 309 Series
Page 1: ...Power Supply Module Technical Information L 309 150 L 309 250 104 Edition ...
Page 3: ......
Page 5: ...Flexible Automation Type L 309 Power Supply Module 1070 078 131 104 00 05 GB ...
Page 15: ...Flexible Automation Type L 309 Power Supply Module Structure 2 1070 078 131 104 00 05 GB ...
Page 27: ...Maintenance Type L 309 Power Supply Module 14 1070 078 131 104 00 05 GB ...
Page 31: ...Dimensioning instructions Type L 309 Power Supply Module 18 1070 078 131 104 00 05 GB ...
Page 33: ...Fault messages Type L 309 Power Supply Module 20 1070 078 131 104 00 05 GB ...
Page 36: ...A 1 1070 078 131 104 00 05 GB 1070 078 131 104 00 05 GB TI WS AT VWS Printed in Germany ...