42
en | Technical data
NEV 400 LSN Power
supply
2019-11 | 04 | F.01U.309.346
Bosch Security Systems B.V.
9
Technical data
Electrical
Rated voltage in VDC
28 ± 1
Minimum operating voltage in VDC
26
Maximum operating voltage in VDC
30
Minimum output voltage in VDC
24
Maximum output voltage in VDC
30
Rated current in mA
500 mA
Maximum output current in A (A or B) 2
Maximum output current in A (A and
B)
3
AC failure detection delay
10 min
Battery ampere hour rating
2 x 12 V / 18 Ah
Mechanical
Dimension in cm (H x W x D)
43,6 x 44,3 x 11,2
Environmental
Environmental class
II
Protection class
IP30