Maintenance
At least once a year, a walk test should be performed to verify the range and coverage for
proper operation.
Magnet walk test
Perform a magnet test to ensure proper functionality of the door and window contacts.
Magnet testing can be performed by opening or closing the door/window in which the magnet
is installed. In this test, you are verifying the distances of which the magnet engages and
disengages the transmitter.
Complete the installation
Depending on the results of testing the RADION system from a system-wide approach (walk
test, signal strength and margin tests), make the appropriate modifications/adjustments to
complete the install process.
RFRC-OPT system test
Overall system test
It is recommended by to test the entire system at least once every year, including the RFRC-
OPT receiver by an installer to ensure proper functionality of the RADION system.
External LED states
The receiver utilizes the External LED to show various states of the receiver. These states fall
into the following three categories:
–
Normal state
–
Communication error state
–
Trouble state
–
Maintenance state
–
Off state
Normal state:
The receiver enters a normal state when it has passed all power self-tests and has established
a communication link with the control panel . The receiver remains in this state as long as the
communication link is present, and no other issues are present that would prevent the
receiver from operating in a normal condition.
LED condition
State description
On (Normal)
Indicates the receiver is functioning normally.
Continuous slow flash: 1 sec On, 1 sec Off
Indicates the receiver is being programmed
with the zone and transmitter ID’s from the
compatible control panel.
Turns Off momentarily
Indicates the receiver obtained a valid
transmission from a RADION transmitter.
Flash 3 times
Indicates the receiver has obtained a new
device ID while in “Learn Mode.”
3.2.7
3.2.8
3.3
RADION receiver OP
RADION receiver OP | en
15
Bosch Security Systems, Inc
Reference Guide
02.2014 | 01 | F.01U.261.835