①
Motor housing
②
Terminal box
③
Holding Brake (Optional)
④
Equipotential bonding connection at the motor (only available on
ATEX motors)
⑤
Equipotential bonding connection at the machine (necessary for ATEX
motors)
⑥
Rexroth drive controller
Fig.6-11:
Double cabling connection diagram
●
The terminal box can only be used for double cabling where
power connection is concerned.
●
Fuses F1 (NH...) protecting the wires against overload in
case of a cable break must be dimensioned according to the
current carrying capacity of the particular line cross-section.
●
The fuses should be installed in the control cabinet such that
they are as close as possible to the power output of the con‐
troller.
●
The shield of the motor power cable must be connected to
the control cabinet on the motor side of the fuses such that it
is conducting over a large area.
●
Power cables are not available to establish the double ca‐
bling. To install the fuses, standard Rexroth power cables
must be opened and cut to the appropriate length on site.
Bosch Rexroth AG
DOK-MOTOR*-2AD********-IT01-EN-P
Rexroth 2AD Asynchronous Housing Motors
40/61