![background image](http://html.mh-extra.com/html/bosch/rexroth-efc-3600/rexroth-efc-3600_operating-instructions-manual_40573151.webp)
Minimum immunity requirements for PDSs intended for use in the first environment
Port
Phenomenon
Basic
standard
for test
method
Level
Performance
(acceptance)
criterion
Enclosure port
ESD
IEC
61000-4-2
4 kV CD or 8 kV AD
if CD impossible
B
Radio-frequency electro‐
magnetic field, amplitude
modulated
IEC
61000-4-3
80 – 1000 MHz 3 V/m
1.4 – 2.0 GHz 3 V/m
2.0 – 2.7 GHz 1 V/m
80% AM (1 kHz)
A
Power ports
Fast transient-burst
IEC
61000-4-4 1 kV/5 kHz
B
Surge 1.2/50 μs, 8/20 μs
IEC
61000-4-5 1 kV
a
, 2 kV
b
B
Conducted radio-frequen‐
cy common mode
IEC
61000-4-6
0.15 – 80 MHz 3 V
80 % AM (1 kHz)
A
Power interfaces
Fast transient-burst
IEC
61000-4-4
1 kV/5 kHz
Capacitive clamp
B
Ports of process measurement control lines
Fast transient-burst
IEC
61000-4-4
0.5 kV/5 kHz
Capacitive clamp
B
Conducted radio-frequen‐
cy common mode
IEC
61000-4-6
0.15 – 80 MHz 3 V
80 % AM (1 kHz)
A
Fig.11-2: Minimum immunity requirements for PDSs intended for use in the first envi‐
ronment
● CD: Contact discharge.
● AD: Air discharge.
● AM: Amplitude modulation.
●
c
: Coupling line to line.
●
d
: Coupling line to earth.
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Bosch Rexroth AG
Electromagnetic Compatibility (EMC)
149/235