b1.30 Starting mode
0: Start directly
1: Braking before start
2: Start with speed capture
1
0
STOP
b1.31
Starting
frequency
0.00 ~ 50.00 Hz
0.01 Hz 0.05 Hz STOP
b1.32
Starting
frequency
holding time
0.0 ~ 20.0s
0.1s
0.1s
STOP
b1.33
Starting DC
braking time
0.0 ~ 20.0s (0.0 represents
no
action of starting DC braking)
0.1s
0.0s
STOP
b1.34
Starting DC
braking current
0.0 % ~ 150.0 %
(Rated frequency converter
current)
0.1 %
0.0 %
STOP
b1.35
~
b1.39
Reserved
–
–
–
–
Stopping configuration
Function
code
Name
Setting range
Min. unit Factory
default
Attribute
b1.40 Stopping mode
0: Deceleration to stop
1: Freewheeling to stop
2: Freewheeling under
STOP-command, decelerat‐
ing under direction change
1
0
STOP
b1.41
Stopping DC
braking initial
frequency
0.00 ~ 50.00 Hz
0.01 Hz 0.00 Hz
STOP
b1.42
Stopping DC
braking time
0.0 ~ 20.0s
(0.0 represents no action of
stopping DC braking)
0.1s
0.0s
STOP
Bosch Rexroth AG
Appendix
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
202/235
Summary of Contents for Rexroth EFC 3600
Page 6: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 IV 235 ...
Page 232: ...230 235 ...
Page 236: ...Bosch Rexroth AG DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 234 235 ...
Page 237: ...Notes DOK RCON03 EFC 3600 IT01 EN P Rexroth Frequency Converter EFC 3600 Bosch Rexroth AG ...