17.2.12
Group H0: Communication
General communication configuration
Function
code
Name
Setting range
Min.
unit
Factory
default Attribute
H0.00 Communication
protocol
0: ModBus
1
0
STOP
H0.01 Baud rate
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
1
3
STOP
H0.02 Data format
0: N, 8, 1 (1 start bit, 8 data
bits, 1 stop bit, no check)
1: E, 8, 1 (1 start bit, 8 data
bits, 1 stop bit, even parity)
2: O, 8, 1 (1 start bit, 8 data
bits, 1 stop bit, odd parity)
2: N, 8, 2 (1 start bit, 8 data
bits, 1 stop bit, no parity)
1
0
STOP
H0.03 Local address
1 ~ 247
1
1
STOP
H0.04
~
H0.07
Reserved
–
–
–
–
H0.08
Communication
disruption de‐
tection time
0.0 (invalid),
0.1 ~ 60.0s
0.1s
0.0s
STOP
H0.09 Communication
disruption action
0: Freewheeling stop
1: Keep running
1
1
STOP