b1.17
The second RUN command source
Setting range
0 ~ 2
Minimum unit
1
Factory default 0
● 0: Inputting commands with operating panel
● 1: Inputting commands via external terminals
● 2: Inputting commands via communication
b1.20
Acceleration time 1
Setting range
0.1 ~ 6000.0s
Minimum unit
0.1s
Factory default 5.0s
b1.21
Deceleration time 1
Setting range
0.1 ~ 6000.0s
Minimum unit
0.1s
Factory default 5.0s
Fig.8-5: Acc. / Dec. time
For EFC 3600, acceleration / deceleration time is defined as the time from zero to the
Max. frequency and from the Max. frequency to zero. 4 groups of acceleration / decel‐
eration time are available, which can be selected via external terminals. For related set‐
tings, please see [E0.01] ~ [E0.05] and [E2.00] ~ [E2.05].
Jog function has its own acceleration and deceleration time.