– REV input is level-sensitive
– Preselect the direction before setting RUN command, otherwise direction will
change (with a possible "dead zone time").
● When setting [E0.00] "2-wire / 3-wire running control", 3-wire control
can only be selected after the 3-wire input terminal has been mapped.
Otherwise, “PrSE” warning occurs.
● When setting [E0.01] ~ [E0.05], the 3-wire input terminal can only be
unselected after the 3-wire control has been disabled. Otherwise,
“PrSE” warning occurs.
E0.01
Terminal X1
Setting range
0 ~ 28
Minimum unit
1
Factory default 0
E0.02
Terminal X2
Setting range
0 ~ 28
Minimum unit
1
Factory default 0
E0.03
Terminal X3
Setting range
0 ~ 28
Minimum unit
1
Factory default 0
E0.04
Terminal X4
Setting range
0 ~ 28
Minimum unit
1
Factory default 0
E0.05
Terminal X5
Setting range
0 ~ 28
Minimum unit
1
Factory default 0
5 external digital input terminals are available with PNP and NPN input modes.
● 0: No action (The frequency converter has no action even if there is input signal.
Multiple selection is possible.)
● 1: Multi-speed terminal 1
● 2: Multi-speed terminal 2
● 3: Multi-speed terminal 3
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Bosch Rexroth AG
Parameter Settings
93/235