Index
Object name
Object
type
Data type
A
L [byte]
Rights
Meaning
.5
MoreFollows
Var
Unsigned 8
1
1
R
Further information on the malfunc‐
tion:
00 - Channel number can be read out
via DiagStateChannelNo, refer to
chapter 9.1.3 "DiagStateChannelNo
01 - Further information can be read
out via the DiagStateLong object
02 - AddValue can be read out via Di‐
9.1.4 "DiagStateAddValue object
04 - One group is affected
08 - One module is affected
.6
Text
Var
Visible string 1
50 + 1
max.
R
Plain text message; default: Status
OK
Tab. 9-5:
DiagState object
9.1.3
DiagStateChannelNo object 0x0033
If it is specified under MoreFollows in the DiagState object that a channel
number is available, it can be determined via the DiagStateChannelNo object
0x0033.
Index
Object name
Object
type
Data type
A
L [byte]
Rights
Meaning
0x0033 DiagState
Record
6
R
Diagnostic state
.1
Lfd.Nr.
Var
Unsigned 16 1
2
R
Consecutive fault number since last
reset or error memory reset
.2
ChannelNo
Var
Unsigned 8
1
1
R
Affected channel
Tab. 9-6:
DiagStateChannelNo object
9.1.4
DiagStateAddValue object 0x0034
If it is specified under MoreFollows in the DiagState object that an AddValue
number is available, it can be determined via the DiagStateAddValue object
0x0034.
Index
Object name
Object
type
Data type
A
L [byte]
Rights
Meaning
0x0033 DiagState
Record
6
R
Diagnostic state
.1
Lfd.Nr.
Var
Unsigned 16 1
2
R
Consecutive fault number since last
reset or error memory reset
.2
AddValue
Var
Unsigned 32 1
4
R
Associated value to the fault code
(parameterization error), refer to
chapter 9.2.4 "Parameterization er‐
Tab. 9-7:
DiagStateAddValue object
DOK-CONTRL-S20*SSDO*8*-AP02-EN-P
Bosch Rexroth AG
45/85
IndraControl S20 Module With Safe Digital Outputs S20-SSDO-8/3
Errors: Reporting and troubleshooting