VAU 01.1U/VAU 01.1S
VAU 01.1Z
Fig. 10-1: Mounting rail holders on the rear panel of the UPS
●
The LED displays have to be visible
●
Provide the following minimum distances for sufficient cooling and cable
routing:
– To the bottom side 50 mm
– To the top side 80 mm
– To the front side 85 mm
●
Provide the cables with a strain relief
●
Keep as much distance as possible to noise sources, when installing the UPS
10.2 Housing Dimensions
The UPS has the following dimensions:
UPS
Width
Height
Depth
(without connector)
VAU 01.1U/VAU 01.1S
123 mm
145 mm
128 mm
VAU 01.1Z
70 mm
145 mm
133 mm
Tab. 10-1: Dimensions
VAU 01.1
Bosch Rexroth AG
Assembly, Disassembly and Electrical Installation
DOK-SUPPL*-VAU*01.1X**-IT02-EN-P
19/53