Switch time
> 120 seconds
Switch position 2; UPS time approx. 120 s
Computer
shutdown
"Shutdown Delay
Time"
(is set in the
UPS NT Control
software)
> 120 seconds
remaining time
of the set switch
position
approx. 40 s
24V In Input voltage DC 24 V on the UPS of the power supply unit
24V Out Output voltage DC 24 V of the UPS to supply the connected PC
Fig. 12-3: Timing for rotary switch S1 in position "2"
Switch position 8, Shutdown Delay Time = 45 seconds
Switch time
> 120 seconds
Switch position 8; UPS time approx. 240 s
Computer
shutdown
"Shutdown Delay
Time"
(is set in the
UPS NT Control
software)
> 120 seconds
remaining time
of the set switch
position
approx. 160 s
24V In Input voltage DC 24 V on the UPS of the power supply unit
24V Out Output voltage DC 24 V of the UPS to supply the connected PC
Fig. 12-4: Timing for rotary switch S1 in position "8"
Observe that the timing behavior depends on the switch position "and" on the
"Shutdown Delay Time", which is set in the "UPS-NT Control" software. Via this
software times from 1 second to 45 seconds can be set.
13 Error Causes and Elimination
Device states are indicates on the front panel via LED.
The arrangement of the LED on the front panel is shown in
rating and Error Display" on page 34
.
Bosch Rexroth AG
Error Causes and Elimination
VAU 01.1
38/53
DOK-SUPPL*-VAU*01.1X**-IT02-EN-P