4.3
Ambient Conditions
In operation
Transport
Storage
Ambient tempera‐
ture
+5 °C to +45 °C
-20 ℃ to +60 ℃
-20 ℃ to +60 ℃
Maximum tempera‐
ture gradient
Temporal tempera‐
ture changes up to
3 ℃ per minute
Temporal tempera‐
ture changes up to 3
℃ per minute
Temporal temper‐
ature changes up
to 3 ℃ per minute
Relative humidity
Climatic class 3K3
according to
EN 60721, conden‐
sation not permissi‐
ble.
Max. 80 % humidity
at 25 °C
Climatic class 3K3
according to
EN 60721, conden‐
sation not permissi‐
ble.
Max. 80 % humidity
at 25 °C
Climatic
class
3K3 according to
EN 60721, con‐
densation not per‐
missible.
Max. 80 % humid‐
ity at 25 °C
Air pressure
Up to 3000 m
above sea level
acc. to EN 61131-2
Up to 3000 m above
sea level acc. to EN
61131-2
Up to 3000 m
above sea level
acc.
to
EN
61131-2
Mechanical
strength
Maximum vibration
Frequency range:
10 Hz to 150 Hz
Excursion:
0.075
mm at 10 Hz to 57
Hz
Acceleration: 1 g at
57 Hz to 150 Hz
Test duration for
each axis: 10 fre‐
quency cycles
Frequency sweep
rate:
1 octave/min
According to EN
60068-2-6, test Fc
Maximum shock:
15 g according to EN
60 068-2-27, no dis‐
turbance of the func‐
tion
Maximum shock:
15 g according to
EN 60 068-2-27,
no disturbance of
the function
Degree of pollution 2
2
2
Fig.4-4:
Ambient Conditions
4.4
Standards
4.4.1
Used Standards
The system components of the VAU 01.1U comply with the following stand‐
ards:
Standard
Meaning
EN 60 61000-6-4
Generic standard, emitted interference (industrial environ‐
ment)
EN 60 61000-6-2
Generic standard, noise immunity (industrial environment)
Bosch Rexroth AG
DOK-SUPPL*-VAU*01.1U**-PR03-EN-P
Rexroth IndraControl VAU 01.1U UPS with USB interface
22/63
Technical Data