7 Technical data
7.1 Degree of protection and weight
Degree of protection
IP 20
Weight
0.94 kg
Tab. 7-1: Degree of protection and weight
7.2 Input and output voltage
Nominal input voltage
24 V DC (use a 24 V power supply unit acc. to DIN EN
60742, classification VDE 0551, for example the power sup-
ply unit VAP01.1H-W23-024-010-NN, part number
R911171065)
Input voltage range
24 V DC +20 %, -20 %
Current consumption at U
N
4.2 A
Current consumption (max.) at U
N
-20% 5.2 A
Max. power consumption
100 W
Tab. 7-2: Input voltage 24 V
Nominal output voltage
24 V DC
Current output at U
N
3 A max.
Bridging time
3 minutes max. if battery charged by 50%
5 minutes max. if battery charged by 85%
Max. output power
72 W
Short-circuit protection
Yes
Tab. 7-3: Output voltage 24 V
Explosion hazard due to short-circuiting of the
connections
CAUTION
Do not short-circuit the UPS connections.
Overheating and possible damage to the UPS if
the max. power consumption is exceeded.
NOTICE
The max. power consumption of the connected control cabinet or panel PC must
not exceed the max. output power of the UPS of 72 W.