7.4 Response upon voltage failure
The UPS response upon voltage failure is described in the following.
PC failure due to faulty operation!
NOTICE
After the UPS has been issued the shutdown command, wait until the UPS buf-
fer time elapses before disconnecting the connecting cable to the PC or restart-
ing the PC.
Normal
mode
24 V In
UPS switch-off 150 s
after voltage failure
24 V Out
Time between shutdown command
and UPS switch-off: 120 s
PC shutdown
24 V Out
24 V In
UPS switch-off 150 s
after voltage failure
Default: 30 s
Time between voltage
failure and issuing
shutdown command
24 V Out
24 V In
No UPS switch-off, as
voltage failure <30 s
2
10 to 180 s
+120 s
0 s
Time of
voltage failure
completed
PC shutdown
1
①
The connection between PC and UPS may neither be disconnected nor established again
during this period! If the connection is restored, the PC restarts and there is an uncon-
trolled switch-off when the UPS buffer time elapses.
②
The period between the voltage failure and the shutdown can be set between 10 and 180
seconds in the dashboard; "Time to Shutdown after Power Outage"
Fig. 7-1: Pulse diagram of the UPS