R911323106
/
02
|
Rexroth IndraControl VCP 35.2
Electric Drives and Controls |
Bosch Rexroth AG
4
-5
Technical Data
Humidity
Operation
Minimum Relative Humidity: 5%
Maximum Relative Humidity: 85%
Minimum Absolute Humidity: 1 g/m
3
Maximum Absolute Humidity: 25 g/m
3
No Condensation Permitted
According to the Clima Class 3K3 to EN 60721-3-3
Transportation
Minimum Relative Humidity: 5%
Maximum Relative Humidity: 75%
Minimum Absolute Humidity: 1 g/m
3
Maximum Absolute Humidity: 25 g/m
3
No Condensation Permitted
According to the Clima Class 2K2 to EN 60721-3-2
Storage
Minimum Relative Humidity: 5%
Maximum Relative Humidity: 85%
Minimum Absolute Humidity: 1 g/m
3
Maximum Absolute Humidity: 25 g/m
3
No Condensation Permitted
According to the Clima Class 1K2 to EN 60721-3-1
Atmospheric
Pressure
Operation
To 2000 m about Sea Level According to DIN EN 61131-2
Transportation
To 3000 m about Sea Level According to DIN EN 61131-2
Storage
To 3000 m about Sea Level According to DIN EN 61131-2
Mechanical
Strength
Operation
Maximum Vibration:
Frequency Range: 10 Hz to 150 Hz
Deflection: 0,075 mm (0.003") at 10 Hz to 57 Hz
Acceleration: 1 g at 57 Hz to 150 Hz
According to DIN EN 60068-2-6
Transportation,
Storage
Maximum Shock:
15 g 11 ms According to DIN EN 60068-2-27, No Distur-
bance of the Function
Application Area
Operation
Degree of Pollution 2, Overvoltage Category II
Transportation,
Storage
Degree of Pollution 2
Environmental Conditions