If multiple XM2x controls (24 V supply voltage U
LS
) are connected
parallely to a central 24 voltage supply, ensure that the 0 V connec-
tion of the U
LS
is wired without interruption to all XM2x controls.
If this is not observed, XM2x might become defective.
Power connector XD1
a1
b1
b2
a2
Fig. 10-14: Power connector XD1
Plug contact
Signal
Function
a1, a2
24 V
+24 V DC supply voltage (U
LS
)
b1. b2
0 V
GND (U
LS
) (ground supply voltage)
Tab. 10-1: Pin assignment of the power connector XD1
In the power connector, the contact a1 is bridged with a2 and the
contact b1 is bridged with b2. The control is set up to connect to a
UPS in future variants. Thus, 2A is labeled with "UPS". However, a
UPS can only be used without bridges when a respective variant and
a specific power connector are used.
10.7.3 24 V voltage supply
The voltage of 24 V can be supplied with or without electrical isolation.
Setup without electrical isolation
An easy connection method is the setup without an electrical isolation between
the internal logic and the peripheral supply.
In this case, a power supply unit is sufficient to supply the control.
The GND (U
LS
) is grounded in the device!
IndraControl XM21, XM22 Controls
27/69
Mounting, demounting and electric installation
R911340667_Edition 04 Bosch Rexroth AG
Summary of Contents for Rexroth IndraControl XM21
Page 1: ...IndraControl XM21 XM22 Controls Operating Instructions R911340667 Edition 04 ...
Page 6: ...IV IndraControl XM21 XM22 Controls Bosch Rexroth AG R911340667_Edition 04 ...
Page 70: ...64 69 IndraControl XM21 XM22 Controls Bosch Rexroth AG R911340667_Edition 04 ...
Page 73: ...IndraControl XM21 XM22 Controls 67 69 R911340667_Edition 04 Bosch Rexroth AG ...
Page 74: ...68 69 IndraControl XM21 XM22 Controls Bosch Rexroth AG R911340667_Edition 04 ...