Rexroth IndraDrive
Electrical Installation
7-5
DOK-INDRV*-HMV-*******-PR01-EN-P
Optimal EMC Installation
With regard to an optimal EMC installation, a spatial separation of the
interference-free area (mains connection) and the interference
susceptible area (drive components) is advisable. See the next figure in
this respect.
HMV01.1E-Wxxxx
mains
PE
mains
filter
load
earth rail
to the motors
power connection
shielded control cabinet
compartment or intermediate
panel
control
cabinet
connecting
clamps
main
switch
distributor
clamps
fuse
HMVE_emv.fh7
supply unit
dr
iv
e controller
dr
iv
e controller
mains
choke
Fig.
7-1:
HMV01.1E - Separation of interference-free and interference
susceptible areas