7-26
Electrical Installation
Rexroth IndraDrive
DOK-INDRV*-HMV-*******-PR01-EN-P
hmv_X31_schalt
ready for operation
DC bus
ok
warning
overtemperature/
bleeder overload
Bb1
UD
WARN
6
5
4
3
2
1
X31
Name
Pin no.
Description
Level
Notes
Bb1_1
6
Bb1_2
5
supply unit ready for
operation
contact
load DC 30V / 1A
inrush current max. 5A
contact closes:
if no error is present
contact opens:
if error is present
UD_1
4
UD_2
3
power supply ok
contact
load DC 30V / 1A
inrush current max. 5A
contact closes:
if DC bus voltage is within the specified
range
contact opens:
if DC bus voltage is too low resp. in case
of mains failure
WARN_1
2
WARN_2
1
warning signal for bleeder
overload and
overtemperature
contact
load DC 30V / 1A
inrush current max. 5A
contact closes:
in case of bleeder overload resp.
overtemperature
contact opens:
setting by default
Fig. 7-27: Connection X31
Connection
Summary of Contents for Rexroth IndraDrive HMV01.1E-W0030
Page 30: ...5 2 Transport and Storage Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 40: ...6 10 Mechanical Mounting Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 88: ...9 8 Control Mains Contactor Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 122: ...13 22 Appendix Rexroth IndraDrive DOK INDRV HMV PR01 EN P Fig 13 25 HFD01 2 480 0026 ...
Page 123: ...Rexroth IndraDrive Appendix 13 23 DOK INDRV HMV PR01 EN P Fig 13 26 HFD02 2 480 0026 ...
Page 130: ...14 6 Index Rexroth IndraDrive DOK INDRV HMV PR01 EN P Notes ...
Page 131: ......