7-30
Electrical Installation
Rexroth IndraDrive
DOK-INDRV*-HMV-*******-PR01-EN-P
X14, Mains Voltage Synchronization
The X14 interface is only available for regenerative supply units
(HMV01.1R). It is used to connect the mains voltage synchronization.
hmv_X14
3
2
1
Fig. 7-36:
X14
Type
Number of poles
Type of design
LE 7,62 M PC 4,0 / 3G
3
Connector on device
Fig. 7-37:
Design
Cross section
single-wire
[mm²]
Cross section
multiwire
[mm²]
Cross section
in AWG
Gauge No.
1,5 - 4
1,5 - 4
16 - 12
Fig. 7-38:
Connection cross section
Pin no.
Description
Level
Notes
3
mains connection phase L3 before choke
max. 900V
current load max. 5A
2
mains connection phase L2 before choke
max. 900V
current load max. 5A
1
mains connection phase L1 before choke
max. 900V
current load max. 5A
Fig. 7-39: Connection X14
Description
Graphic Representation
Design
Connection cross section
Connection