C1804 Automatic controller setting failed
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
In exceptional cases difficulties can occur during automatic control loop
setting. This means that automatic setting is impossible and the default or
standard values are loaded to the drive again.
Causes:
•
oscillating mechanical systems (resonances)
•
highly noisy encoder signals
Remedy:
It is sometimes possible to achieve a satisfactory result by restarting the
command
P-0-0162, C1800 Command Automatic control loop adjust
with a high
P-0-0163, Damping factor for autom. controller adjust
, i.e.
a low degree of dynamic response.
This value then can still be reduced until the desired control loop behavior
occurs.
See also Functional Description "Automatic Setting of Axis Control"