Rexroth IndraDrive
Error Messages
7-19
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F8100 Error during initialization of control section
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the initialization of the drive the control section is checked for
correct function. An error was detected during this check.
Cause
Remedy
Control section configuration not allowed because an
optional module (e.g. optional module 1...4, master
communication,...) is not supported by firmware
Switch drive off and on again. If error occurs again,
replace control section (e.g. CSH01.1 or CDB01.1) by
different control section with appropriate configuration.
If necessary, contact our service department
Firmware used is not suitable (e.g. MPH02VRS for
double-axis control section), i.e. hardware and
software do not match
Select suitable firmware by means of Functional
Description or Version Notes/Release Notes
(see "supported control section configurations")
Hardware defect on control section
Switch drive off and on again. If error still occurs,
contact our service department and, if necessary,
replace control section or entire drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
See also Functional Description "System Overview"
See also Project Planning Manual for control section, keyword "Type
Code"
F8100 - Attributes
Display:
F8100
Mess. no.:
F8100 (hex)
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01