7-24
Error Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F8133 Error when checking interrupting circuits
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
In order to lock the output stage in a safety related way when the safety
technology has detected an error, the correct functioning of the
interrupting circuit is cyclically checked. This is done on the one hand
during the actions "release output stage" and "lock output stage", on the
other hand statically while the output stage is being released or locked.
The corresponding hardware realization ensures that this is possible
without repercussion on the PWM control signals.
The drive torque is immediately disabled. The drive automatically
switches to "safety related standstill" and the output stage is switched off
via one channel. All poles of the mains contactor are switched off.
Note:
Safety is not acknowledged; i.e. "safety technology status
output controller" was cleared/reset in
P-0-3214, Safety
technology signal status word, channel 1
or the diagnosis
input/output I/O10n (channel 2) was set depending on the
parameterization in
P-0-3210, Safety technology control
word
.
Cause
Remedy
An error was detected during check of interrupting
circuit
Error cannot be cleared. Switch power supply off and on
again.
If error occurs repeatedly, replace control section or
entire drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
F8133 - Attributes
Display:
F8133
Mess. no.:
F8133 (hex)
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01