Rexroth IndraDrive
Error Messages
7-93
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F2040 Device overtemperature 2 shutdown
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
A switch-off value for the second temperature sensor is stored in
element 3 of parameter
P-0-4059, Electric type data of power section
.
If parameter
P-0-0816, Amplifier temperature 2
exceeds the switch-off
value, the error F2040 is generated and the device is switched off.
Cause
Remedy
Ambient temperature too high. Specified
performance data are valid up to an ambient
temperature of 40 C.
Reduce ambient temperature, e.g. by cooling the control
cabinet
Heat sink of device is dirty
Clean heat sink
Convection is prevented by other components or
mounting position in control cabinet
Mount device vertically and provide sufficient space for
ventilating heat sink
Blower of device is defective
Replace device
F2040 - Attributes
Display:
F2040
Mess. no.:
F2040 (hex)