Rexroth IndraDrive
Error Messages
7-103
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F2069 Error when releasing the motor holding brake
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the automatic check of the holding brake (
P-0-0525, Holding
brake control word
), after drive enable or after the start of the
P-0-0541,
C2100 Brake check command
the motor did not move, although half the
holding torque was produced.
Note:
The result of the brake check is displayed in
P-0-0539,
Holding brake status word
.
Cause
Remedy
Motor brake (servo brake) was not or incorrectly
connected
Connect brake or correct connection
Axis is mechanically blocked
Check mechanical system and remove blocking
Brake is defective
Check and, if necessary, replace brake
Brake supply error
Check voltage
Friction torque of axis is greater than test torque of
drive
Deactivate brake check (
P-0-0525, Holding brake
control word
) because it cannot be used due to
mechanical properties
F2069 - Attributes
Display:
F2069
Mess. no.:
F2069 (hex)