7-114
Error Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F2110 Error in non-cyclical data communic. of power section
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
Supported by Supply Unit:
HMV01
An error occurred in the communication between control section and
power section.
Cause
Remedy
Failure occurs sporadically (firmware error)
Clear error and contact our service department for
firmware update
Hardware defective
Should error occur repeatedly, control section or entire
device has to be replaced
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
F2110 - Attributes
Display:
F2110
Mess. no.:
F2110 (hex)