8-16
Warning Diagnostic Messages (Exxxx)
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
E3103 Dynamization failed
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
When the safety technology has been activated, this warning only occurs
in normal operation. When a safety function is selected, the cause of the
error causes the error
F3134 Dynamization time interval incorrect
or
F3135 Dynamization pulse width incorrect
to be triggered.
Cause
Remedy
There doesn
’
t occur any dynamization pulse at the
dynamization input within the time
P-0-3223, Time
interval for dynamization of safety function
selection
or the pulse width differs from the
parameterized time
P-0-3224, Duration of
dynamization pulse of safety function selection
Remove cause of error in wiring of dynamization input
E3103 - Attributes
Display:
E3103
Mess. no.:
E3103 (hex)
E3104 Plausibility error of safety parameters
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
When the safety technology has been activated, this warning only occurs
in normal operation. When a safety function is selected, the cause of the
error causes the error
F3140 Plausibility error of safety parameters
to
be triggered.
Cause
Remedy
A comparison has shown that channel 1 and
channel 2 are not working with the same safety
parameters
Execute command
P-0-3204, Synchronize and store
safety technology IDN command
; channel 2 thereby
accepts parameters of channel 1
E3104 - Attributes
Display:
E3104
Mess. no.:
E3104 (hex)