Rexroth IndraDrive
Warning Diagnostic Messages (Exxxx)
8-29
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
E2055 Feedrate override S-0-0108 = 0
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
By means of the
S-0-0108, Feedrate override
it is possible to make a
proportional scaling for the travel velocity of drive-controlled travel
commands (0..100 %).
A feedrate override of 0 % causes the effective travel velocity to become
"0". In spite of velocity command value being present (e. g.
S-0-0259,
Positioning velocity
), the drive remains stopped at the current position
or brakes down until reaching standstill.
Note:
The function of the feedrate override can be switched off by
setting S-0-0108 = 100 %.
If S-0-0108 has been cyclically configured or assigned to an
analog input, this configuration has to be changed.
Cause
Remedy
Parameter
S-0-0108, Feedrate override
was set to
"0"
Set feedrate override > "0" so that drive moves. Full
velocity is reached with 100%.
For devices with analog inputs: feedrate override via
analog input has been activated and voltage at
analog input is "0"
Apply voltage > "0" proportionally to desired velocity
(+10 V corresponds to 100% of velocity)
alternative: deactivate feedrate override
Infeed potentiometer of connected control unit was
set to "0" or is incorrectly evaluated
Carefully actuate infeed potentiometer, check analog
signal and evaluation
Analog input used for feedrate override or
connecting cable is defective
Check and if necessary replace cable and control
section
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
E2055 - Attributes
Display:
E2055
Mess. no.:
E2055 (hex)
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01