DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C0501 Error clearing only in parameter mode
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the error clearing command (C0500) an error was
detected.
Cause:
There was an attempt to clear the
F8022 Enc. 1 error: sign. amplitude
(can be cleared in ph.2)
error in communication phase 4 (operating
mode). This is only possible in communication phase 2 (parameterization
mode).
Remedy:
Switch the drive in communication phase 2 by means of the
P-0-4023,
C400 Communication phase 2 transition
command and start the error
clearing command again.
C0501 - Attributes
Display:
C0501
Mess. no.:
C0501 (hex)
C0601 Homing only possible with drive enable
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the "Drive-controlled homing procedure"
command (C0600) an error was detected.
Cause:
The command was started without drive enable. This is not allowed.
Remedy:
Enable the drive and start the command again.
See also Functional Description "Drive-Controlled Homing"
C0601 - Attributes
Display:
C0601
Mess. no.:
C0601 (hex)