Rexroth IndraDrive
Command Diagnostic Messages
9-71
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C0602 Distance home switch - reference mark erroneous
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the command for drive-controlled homing (C0600)
an error was detected.
Cause:
The evaluation of the home switch has been switched on (
S-0-0147,
Homing parameter
). The distance between selected home switch edge
and reference mark to be evaluated is outside the allowed range.
Remedy:
Read the value from parameter
S-0-0298, Reference cam shift
and take
it over to parameter
S-0-0299, Home switch offset
- or -
shift the reference cam.
See also Functional Description "Establishing Position Data Reference for
Relative Measuring Systems"
C0602 - Attributes
Display:
C0602
Mess. no.:
C0602 (hex)