9-100
Command Diagnostic Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C2104 Command execution not possible
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
It was impossible to start the "Brake check" command (C2100).
Cause
Remedy
in the
P-0-0525, Holding brake control word
parameter the brake has not been activated
activate the brake in the
P-0-0525, Holding brake
control word
parameter
the value in
P-0-0540, Torque of motor brake
is 0
enter the correct value for
P-0-0540, Torque of motor
brake
See also Functional Description "Motor Holding Brake"
C2104 - Attributes
Display:
C2104
Mess. no.:
C2104 (hex)
C2202 Error when writing data to non-volatile memory
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the execution of the
S-0-0264, C2200 Backup working memory
procedure command
an error occurred.
Cause:
It was impossible to address the active, non-volatile memory (internal
flash memory or MMC, if plugged in) without error.
Remedy:
•
First start the command
S-0-0264, C2200 Backup working memory
procedure command
again. If the error occurs again, then
•
replace MMC (if plugged in) if necessary, then start the command
again. If the error occurs again,
•
contact the service department.
C2202 - Attributes
Display:
C2202
Mess. no.:
C2202 (hex)