32
/48
Analog amplifier RA
| Installation
Bosch Rexroth AG, RE 95230-B/2021-12-01
Table 7: Pin assignment RA2-1
Signal
Description
Pin
Outputs
PWM 1 out
Proportional solenoid output outputs (solenoid 1)
1
PWM 1
Feedback
Ground for proportional solenoid 1
14
PWM 2 out
Proportional solenoid output (solenoid 2)
13
PWM 2
Feedback
Ground for proportional solenoid 2
25
Notice:
The PWM solenoid return lines do not have to be returned to the analog amplifier.
Dig Out
Switching output
7
ERR Ind Out
Error output.
The output is active if:
• voltage supply at pin 19 and/or pin 20 falls below approx. 9 V
• the external sensor supplies (8.4 V and 4.0 V) are faulty
• the circuitry at pin 16 and pin 23 is faulty
15
V mid ext 1
Sensor or potentiometer supply voltage 4.0 V
3
V pos ext 1
Sensor or potentiometer supply voltage 8.4 V
16
V mid ext 2
Sensor or potentiometer supply voltage 4.0 V
11
V pos ext 2
Sensor or potentiometer supply voltage 8.4 V
23
7�4�5 Pin assignment (parallel operation)
The following table shows the important pin assignments for parallel operation.
The other pins are to be wired according to Table 7 "Pin assignment" on page 31.
Table 8: Pin assignment (parallel operation)
Signal
Description
Pin
Inputs
Parallel operation
Connected with +U
Bat
: parallel operation, independent control of both solenoids.
Notice:
If the connection is interrupted, only one output stage is controlled.
9
Potentiometer 1
Potentiometer 2
Function of pins:
16, 23: 8.4 V internal voltage
3, 11:
4 V internal voltage
2, 12:
Signal ground
Differential inputs:
17, 22: inverting input
4, 10:
non-inverting input
The voltage difference is used to generate command values. In order to obtain a maximum
command value, a voltage difference of 4 V has to be applied at the inputs of the differential
amplifier.
17, 16, 4, 3,
2, 23, 22, 12,
11, 10