EMC Manual ServodynT, D
Motor, sensor lines
41
1070 066 074-101
4
Motor lines, sensor lines
4.1
Basic procedures
4.1.1 Cable ducts
In order to avoid highfrequency thermal radiation, power connections
from the switching cabinet to the motor should be laid in completely en
closed metal cable ducts.
In the case of multichamber cable ducts, encoder cable should also be
laid in a separate chamber in the cable duct.
The cable duct is connected over a large area with machine parts and the
switch cabinet.
ÈÈÈÈÈÈÈÈÈÈ
ÈÈÈÈÈÈÈÈÈÈ
Ä
ÄÄ
ÄÄ
ÄÄ
ÁÁ
ÁÁ
Á
Á
É
ÉÉ
ÉÉ
ÉÉ
Lines for inverter
controlled motors
Control lines 400 V
X
,
230 V
X
and 24 V=
Screened lines for
measuring systems
Standard
Fig. 4.1: Cable duct with two chambers
ÈÈÈÈÈÈÈÈÈÈ
Ä
Ä
ÄÄ
ÄÄ
ÄÄ
ÄÄ
ÁÁ
Á
É
É
ÉÉ
ÉÉ
ÉÉ
ÉÉ
Lines for inverter
controlled motors
Control lines 400 V
X
,
230 V
X
and 24 V=
Screened lines for
measuring systems
For measuring systems
with sinusoidal signals
Fig. 4.2: Cable duct with three chambers, necessary for employment of sensitive
measuring systems with sinusoidal signal transmission
ÈÈÈÈÈÈÈÈÈÈ
Ä
Ä
ÄÄ
ÄÄ
ÄÄ
ÄÄ
ÁÁ
ÁÁ
ÁÁ
ÁÁ
É
É
ÉÉ
ÉÉ
ÉÉ
ÉÉ
Lines for inverter
controlled motors
Control lines
400 V
X
and 230 V
X
Screened lines for
measuring systems
and 24 V=
For measuring systems
with sinusoidal signals
and interferenceprone
PLCI/O's
Á
Fig. 4.3: Cable duct with three chambers, necessary for sensitive measuring
systems with sinusoidal signal transmission and PLC control units
with interferenceprone I/O's