80/96
Pressure and flow control system SYDFE1 series 2X, 3X
| Troubleshooting
Bosch Rexroth AG, Edition 10.2021, RE 30011-B
15 Troubleshooting
The following table may assist you in troubleshooting. The table is not exhaustive.
In practice, problems which are not listed here may also arise.
Generally, the state of the SYDFE1 control system is indicated on the front panel.
Fig. 35: Indicator lamps on the front panel
This LED is illuminated when the correct voltage supply is provided for the control
electronics VT 5041-3X.
If this LED is not illuminated, check the following:
• Voltage supply available (U = 21...35 V)
• Check fuse F1
This LED signals a collective fault (or missing enable).
The fault signal can also be measured at pin 2c of the female multi-point connector
and can be used for signaling this to a higher-level control.
The following is valid here:
0 V
→
fault
24 V
→
no fault
The fault signal refers to a collective fault and is composed of the following
individual faults:
• Monitoring of actual pressure value acquisition
• Monitoring of swivel angle sensing
• Monitoring of actual valve value sensing
• Enable not granted
• No supply voltage present or fuse F1 defective
• When monitoring of the control error is activated (jumper J9), excessive control
error (valve command value > +4 V or < -4 V) for longer than 1 sec.
Green LED “Ub“
The red LED “Err“